(4) Inverter specifications (Extended function mode : B group)
Display Function name Category Screen display Initial Remarks
Order Code display EU US JPN
1 Selection of restart mode Set B01 00 00 00
2 Allowable UV time Set B02 1.0 1.0 1.0
3 Retry waiting time Set B03 1.0 1.0 1.0
4 Electronic thermal level Set B12 note note note Rated current of
each inverter
- Electronic thermal level
(2
nd
setting)
Set B212 note note note Rated current of
each inverter
5 Electronic thermal
characteristics
Set B13 01 01 00
- Electronic thermal
characteristics (2
nd
setting)
Set B213 01 01 00
6 Overload restriction
operation mode
Set B21 01 01 01
7 Overload restriction level Set B22 note note note Rated current
* 1.25 for each
inverter
8 Deceleration rate while
overload restriction
Set B23 1.0 1.0 1.0
9 Selection of software lock Set B31 01 01 01
10 Analog meter adjustment Set B81 80 80 80
11 Start frequency adjustment Set B82 0.5 0.5 0.5
12 Carrier frequency Set B83 5 5 12
13 Data initialization or
Trip history clear
Set B84 00 00 00
14 Initialization mode Set B85 01 02 00
15 Frequency converting
value
Set B86 1.0 1.0 1.0
16 STOP key condition Set B87 00 00 00
17 Restart mode after FRS
invalid
Set B88 00 00 00
18 Monitor contents
for OPE-J
Set B89 01 01 01
19 Dynamic braking usage
ratio
Set B90 00 00 00
20 Stopping mode selection Set B91 00 00 00
21 Cooling fan control
selection
Set B92 00 00 00
1-4