23
A093/
A293/
A393
Deceleration (2) time setting 15.0
A094/
A294
Select method to switch to Acc2/Dec2 profile
• 00 2CH input from terminal
• 01 transition frequency
00
A095/
A295
Acc1 to Acc2 frequency transition point 0.0
A096/
A296
Dec1 to Dec2 frequency transition point 0.0
A097 Acceleration curve selection
• 00 Linear • 01 S-curve
• 02 U-shape • 03 Reverse
U-shape
00
A098 Deceleration curve selection
• 00 Linear • 01 S-curve
• 02 U-shape • 03 Reverse
U-shape
00
A101 [OI]–[L] input active range start frequency 00.0
A102 [OI]–[L] input active range end frequency 00.0
A103 [OI]–[L] input active range start current 20.
A104 [OI]–[L] input active range end current 100.
A105 [OI]–[L] input start frequency enable
• 00 Use A101 start value • 01Use 0Hz
01
A111 [O2]–[L] input active range start frequency 0.00
A112 [O2]–[L] input active range end frequency 0.00
A113 [O2]–[L] input active range start voltage –100.
A114 [O2]–[L] input active range end voltage 100.
A131 Acceleration curve constants setting 02
A132 Deceleration curve constants setting 02
Func.
Code
Name / Description
Default
Val ue
–FE/ FU/FR
Set
Val ue