24
“B” Group: Fine-tuning Functions
Func.
Code
Name / Description
Default
Value
–FE/FU/FR
Set
Value
B001 Selection of automatic restart mode
00 Alarm output after trip, automatic restart
disabled
01 Restart at 0Hz
02 Resume operation after frequency
matching
03 Resume previous freq. after freq. matching,
then decelerate to stop and display trip info
00
B002 Allowable under-voltage power failure time 1.0
B003 Retry wait time before motor restart 1.0
B004 Instantaneous power failure / under-voltage trip
alarm enable
00 Disable 01 Enable
02 Disable during stop and ramp to stop
00
B005 Number of restarts on power failure / under-
voltage trip events
00 Restart 16 times 01 Always restart
00
B006 Phase loss detection enable
00 Disable – no trip on phase loss
01 Enable – trip on phase loss
0.00
B007 Restart frequency threshold 1.0
B012/
B212/
B312
Level of electronic thermal setting Rated
current of
each inverter
B013/
B213/
B313
Electronic thermal characteristic
00 Reduced torque 01 Const. torque
02 V/f free-setting
01 / 01 / 00
B015 Free setting, electronic thermal freq. (1) 0.
B016 Free setting, electronic thermal current (1) 0.0
B017 Free setting, electronic thermal freq. (2) 0.
B018 Free setting, electronic thermal current (2) 0.0
B019 Free setting, electronic thermal freq. (3) 0.
B020 Free setting, electronic thermal current (3) 0.0
B021 Overload restriction operation mode
00 Disabled
01 Enabled for accel and constant speed
02 Enabled for constant speed only
03 Enabled for accel, decel, constant speed
01