(4) J-AG (Analog input/output PCB)
SJ300 have two analog outputs, -10 to +10V frequency setting input, and torque limit setting
input. Please refer to the chart 10 for the details.
Item J-AG (J300) SJ300
Spec. Description
Terminal
symbol
Terminal specifications
Terminal
symbol
Terminal specifications
Frequency
setting
SO-L
DC –10 to 10V
Input impedance:
30kohms
Input
Torque limit TRQ-L
DC 0 to10V
Input impedance:
30kohms
O2-L
DC –10 to 10V
Input impedance:
10kohms
MA1-L
DC 0 to 10V
3mA max
Analog
voltage
AM
DC 0 to10V
2mA max
Analog
voltage
Output
Analog
monitor
output
MA2-L
DC 0 to 10V
3mA max
Analog
voltage
AMI
DC 4 to 20mA
Allowable Z:
250ohms
Analog
current
P12-L DC+12V 30mA - -
N12-L DC-12V 30mA - -
Power
source
Interface
power
supply
P24-CM1 DC24V 10mA P24-CM1 DC24V 100mA
Chart 10
Analog input/output comparison chart
Note 1: -10 to +10V frequency setting input and torque limit setting input can be made only from
O2 terminal. They cannot be input simultaneously.
Note 2: SJ300 does not have interface power supply for negative voltage.
Please prepare external power supply when inputting negative voltage at O2 terminal.
(5) J-DG (Digital input PCB)
Please use SJ-DG.