Chapter 4 - Parameter Setting
If the current setting values of the J300 are different form the SJ300 default setting value, you need to change the setting.
Please refer to the following for comparison.
4.1 Monitoring functions
J300 SJ300 Remarks
Function code
No. Name
Digital
operator
Remote
Operator
Default setting
Function
code
(Digital
operator)
Default setting
1 Output frequency setting F2 FS 000.0 F001 0.00 Can be set also by A020 in the case of the SJ300
Multi-speed frequency setting F2 1S 0.0 A021 0.00
2
F2 7S 0.0 A027 0.00
3 Output frequency setting F2 TM 0.0 F001 0.00
4 Jog frequency setting F2 JG 1.0 A038 1.00
Jogging stop mode can be selected by A039 in the case of
the SJ300.
5 Option 1 setting frequency F2 O1 0.0 F001 0.00
6 Option 2 setting frequency F2 O2 0.0 F001 0.00
7 Output frequency monitor d0 FS 0.00 d001 0.00
8 Acceleration time setting 1 F6 ACC1 30.0 F002 30.00
Acceleration time setting 2 F6 ACC1 30.0 F202 30.00
9 2-stage acceleration time setting F6 ACC2 15.0 A092 15.00
10 Deceleration time setting 1 F7 DEC1 30.0 F003 30.00
Deceleration time setting 2 F7 DEC1 30.0 F203 30.00
11 2-stage deceleration time setting F7 DEC2 15.0 A093 15.00
12
Motor pole number setting for rotation speed
monitor
A25 RPM_ 4 - - Not supported by the SJ300; substitutable with b086
13 Motor rotation speed monitor d1 _RPM 0 - - Not supported by the SJ300; substitutable with d007
14 Frequency scaling conversion factor A47 /Hz_ 1.0 b086 1.0
15 Scaled output frequency monitor d3 /Hz_ 0.00 d007 0.00
16 Output current monitor d2 Im_ 0.00 d002 0.00
17 Output current proportion monitor - Im_ 0.0 - -
Not supported by the OPE-J (J300); not supported by the
SJ300
18 Torque monitor - Torque 0 d012 0.0 Not supported by the OPE-J (J300)
19 Manual torque boost value 1 F8 V-Boost Code 11 A042 1.0
Manual torque boost value 2 F8 V-Boost Code 11 A242 1.0
Voltage level is equivalent although the default settings are
different between J300 and SJ300.
20 Manual torque boost frequency adjustment 1 - V-Boost F 10 A043 5.0
Manual torque boost frequency adjustment 2 - V-Boost F 10 A243 5.0
The SJ300 has the different default setting (5%) from that
(10%) of the J300.
21 V/f gain setting - V-Gain 100 A045 100
22 Jog frequency setting A61 Jogging 1.00 A038 1.00
Jogging stop mode can be selected by A039 in the case of
the SJ300.
23 FM terminal analog meter adjustment F10 ADJ 172 b081 60
AM and AMI terminals can be also adjusted independently in
the case of the SJ300.
24 Intelligent input terminal monitor - TERM LLLLLLLLL d005 Note
Note: Displayed by the 4-digit display; intelligent output
terminal monitor is also supported by d006.