Temperature
Caution: The follo
wing storage system components are not supported in
high-temperature environments. Do not operate the following components at
temperatures of 40°C or higher:
■
DB60 dense drive tray
■
Hitachi Vantara-provided service processor (SVP) server
State Controller
DBS, DBL
drive trays Dense intermix drive tray (DB60)
Operating 50°F to 104°F
(10°C to 40°C)
50°F to 104°F
(10°C to 40°C)
50°F to 95°F (10°C to 35°C)
Non-operating 14°F to 122°F
(-10°C to 50°C)
14°F to 122°F
(-10°C to 50°C)
14°F to 122°F (-10°C to 50°C)
Transport,
stor
age
-22°F to 140°F
(-30°C to 60°C)
-22°F to 140°F
(-30°C to 60°C)
-22°F to 140°F (-30°C to 60°C)
Temperature
change rate
(°C/h)
10°C or less
Humidity
State
CBSS, /CBSL
controllers
DBS, DBL drive
trays DB60 drive tray
Operating (%) 8 to 80
Non-operating (%) 8 to 90
Transport, storage
(%)
5 to 95
Maximum wet bulb
temper
ature (°C)
29°C (non-condensing)
Vibration
State
CBSS/CBSL
controller
DBS, DBL drive
trays DB60 drive tray
Operating 2.5 or less (5 to 300Hz)
Environmental specications
Appendix B: System Specications
Hitachi Virtual Storage Platform G350, G370 Hardware Reference Guide 82