151276-L8 Before You Begin Installing
2-5
Note: 33 max battery size for FM (Factory Mutual) installations
18 AH 685 mA 270 mA
35 AH 1370 mA 540 mA
* Required for NFPA 72 Auxiliary Protected Fire Alarm systems for Fire Alarm Service (City Box) and Remote Station
Protected Fire Alarm systems (Polarity Reversal) and Digital Alarm Communicator/Transmitter (DACT).
Table 2-3: Maximum Battery Standby Load
Rechargeable
Battery Size
Max. Load for 24 hrs. Standby,
5 mins. Alarm
*Max. Load for 60 hrs. Standby, 5
mins. Alarm