7847i-E Installation and Setup Guide
1-4
Programming for UL864 Compliance
The 7847i-E provides a programmable supervision features that allows the system to meet the UL864
Commercial Fire requirements. These requirements are in the following table.
This product incorporates field-programmable software. In order for the product to comply with the requirements in the
Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options
must be limited to specific values or not used at all as indicated below.
Program feature or option
Possible settings
Settings permitted in UL 864
Supervision
24 Hours CN 90 Sec
1 Hour 75 Sec
6 Min None
3 Min 30 Day
90 Sec
Must be set to:
3 minutes for UL Comm Fire/Burg or
ULC Active Channel Security.
24hrs for ULC Passive channel
security
Old Alarm Time
10 Minutes 4 Hours
15 Minutes 8 Hours
30 Minutes 12 Hours
1 Hour 24 Hours
2 Hours
4 Hours
8 Hours
12 Hours
24 Hours
Must be 10 minutes.
IP Fault Time
[00-99]
Must be one (01) minute.
Flt Rel ON
[Y], [N]
Must be set to "Y."
ECP MODE PROGRAMMING
Zn6 Trigger Type
Zn7 Trigger Type
(V+)
(V–)
(EOLR)
V+ must be set as inverted and V- as
non-inverted
Delay Zn6
Delay Zn7
[01-15]
[00] = no delay
Must be 00
ZONE TRIGGER MODE
PROGRAMMING
Zn1 Trigger Type
to
Zn8 Trigger Type
(EOLR)
(V+)
(V–)
V+ must be set as inverted and V- as
non-inverted
Delay Zn1
to
Delay Zn8
[01-15]
[00] = no delay
Must be 00