54 Installation instructions / ACS-2 plus
12. Outputs
12.1 Semiconductor outputs
The ACS-2 plus board is provided with 3 semiconductor outputs:
The output 5 (terminal 24)
and the output 6 (ST 5-3) are freely programmable via NetEdit.
The watchdog output (ST 5-2) signals (12V) that at least one watchdog reset occurred
since the last hardware reset.
Transistor in common collector circuit.
Two conditions are possible:
- Transistor conducting ( approx. 12V DC at the output).
- Transistor blocking (open output).
To be observed: Max. current carrying capacity = 50 mA,
short-circuit proof.
12.2 Relay outputs
The ACS-2 plus is fitted with 4 potential-free relay outputs with the following factory settings (see 15.1):
2 door strike relays
The connected strikes with load current function can be checked for tampering (see also
chapter 15.4.1).
1 tamper relay (activated when tampering occurs).
1 alarm relay (activated during operation. It is released in case of an alarm or
when disconnected from the power).
An alarm is released when a watchdog reset occurs while the jumper ST8 is connected.
If the ACS-2 plus fails once, the relays 1 and 2 are so defined that the doors remain closed. It is not possible
to change the definition of these relays. The status of relay 3 (alarm) und relay 4 (tamper) can be defined using
jumper ST16.
Setting the reset status of relay 3 (alarm) and relay 4 (tamper):
Press Reset button and hold
Check if relay 3 (alarm relay) is OK, place jumper ST16 on 2-4 or 4-6, if necessary
Check if relay 4 (tamper relay) is OK, place jumper ST16 on 1-3 or 3-5, if necessary
Release Reset button again.