Installation instructions / ACS-2 plus 63
15.5 Electric safety lock
The electric safety lock is available in a conventionally connectable variant (809) as well as in a BUS version
(809N).
16.5.1 Electric safety lock conventional connection
The differential alarm lines (inputs 5 - 10) must be terminated with 12K1.
Door monitoring
The interior door handle contact activates a door release on the ACS-2 plus. The door can
be passed without the error message "Unauthorized door release".
An external contact, e.g., a magnetic contact, must be used for door monitoring. The bolt
switching contact is only evaluated for positive drive condition when the intrusion detection
system is "disarmed". Its status is only shown when the intrusion detection system is
"disarmed". The bolt switching contact alarm group does not release and store an alarm when
the intrusion detection system is "armed".