EasyManua.ls Logo

Honeywell ADEMCO VISTA-48A - Page 42

Honeywell ADEMCO VISTA-48A
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PROMPT
VALID ENTRIES EXPLANATION
10 Zone Type
Perimeter 03
Zone Type (ZT)
00-24, 77, 82, 90-93 = zone
type (see table at right)
Each zone must be assigned to a zone type, which defines the way in
which the system responds to faults in that zone.
Enter the Zone Type code from the list below:
Note: If 00 is entered, Delete Zone ? will be displayed.
00 = Not used 07 = 24-Hr Audible 20 = Arm–STAY*
01 = Entry/exit #1 08 = 24-Hr Aux 21 = Arm–AWAY*
02 = Entry/exit #2 09 = Fire 22 = Disarm*
03 = Perimeter 10 = Interior w/Delay
23 = No Alarm Resp
04 = Interior Follower 12 = Monitor Zone 24 = Silent Burglary
05 = Trouble Day/Alarm Night 14 = Gas 77 = Keyswitch
06 = 24-Hr Silent 15 = Medical 81 = AAV Monitor Zone
16 = Fire w/Verify 82 = Blockschloss
*5800 button-type transmitters only 90-93 = Configurable
10 Partition
1
Partition No. (P)
1-3 = partition
[] to continue
Enter the Partition number for this zone. Partition 1 is shown
entered.
10 Report Code
1st 01 2nd 00 10
Report Code (RC)
First Digit: 01-09, 10 for A, 11
for B, 12 for C, 13 for
D, 14 for E, 15 for F
00 to disable
Second Digit: same as above
[] to continue
Enter the report code for this zone, which consists of 2 hexadecimal
digits, each in turn consisting of 2 numerical digits. For example, for
a report code of “10,” enter 01 and 00.
For Contact ID
®
, entering any non-zero entry as the first digit
enables the report code for this zone. Refer to the System
Communication section for information about report codes and
formats.
02 HARDWIRE TYPE
EOL 0
Basic Wired Type
0 = EOL; 1 = NC; 2 = NO
3 = zone doubling (ZB)
4 = double-balanced (DB)
[] to continue
This prompt appears only for zone numbers 01-08.
02 Response Time
1
Response Time (RT)
0 = 10mSec 2 = 700mSec
1 = 400mSec 3 = 1.2 seconds
[] to continue
This prompt appears only for basic wired zones 01-08 (zone 02 is
used as an example in display).
NOTE: If zone doubling is used, the response time selected for zones
01-08 automatically applies to each zone’s associated doubled zone.
10 INPUT TYPE
RF TRANS 3
Input Device type (In)
2 = AW (Aux wired zone)
3 = RF (supervised RF
transmitter,
4 = UR (unsupervised RF
transmitter)
5 = BR (unsupervised button
type RF transmitter)
7 = RM (supervised RF motion
detector)
[] to continue
This prompt is skipped for zones 9-16 if zone-doubling was enabled at
“Hardwire Type” prompt.
All of the RF transmitters have one or more unique factory-assigned
input (loop) ID codes. Each of the inputs requires its own
programming zone (e.g., a 5804's four inputs require four
programming zones).
RF Transmitters can be enrolled as one of the following types:
Type and Description
“RF” (Supervised RF): Sends periodic check-in signals, as well as
fault, restore, and low-battery signals. The transmitter must stay
within receiver's range.
“UR” (Unsupervised RF): Sends all the signals that the “RF” type
does, but the control does not supervise the check-in signals. The
transmitter may therefore be carried off-premises.
“BR” (Unsupervised Button RF): Sends only fault signals. It does not
send a low-battery signal until it is activated. The transmitter may
be carried off-premises.
“RM” (Supervised RF Motion Detector): Sends periodic check-in
signals, as well as fault and low- battery signals. The panel ignores
detector restore signals but automatically restores the zone to
“ready” after a few seconds. Intended for facilities with multiple
motion detectors that may fault and restore simultaneously. The
transmitter must remain within the receiver’s range.
RM NOTE: While the system is disarmed, faults from input type RM
devices might not be seen on the keypad display because the automati
c
restore can occur more quickly than the display is refreshed.
NOTES:
For the built-in basic wired zones, the Input Device type is
automatically displayed as HW and cannot be edited.
To change the input type of a previously programmed wireless
device (type RF, UR, BR, RM) to a wired zone (type AW), you must
first delete the transmitter’s serial number
Installation Instructions
5-2

Table of Contents

Other manuals for Honeywell ADEMCO VISTA-48A

Related product manuals