Configurable Zone Type Programming (*83 Menu Mode)
Start Configurable Zone Type Programming Mode by pressing
83
while in Data Programming mode.
Enter Zone Type
(00=quit) 90
Zone Type Number
90-93 = zone type
[] to continue
Enter the configurable zone type number being programmed.
90 Zn Attributes
0
Zone Attributes
0 = none
1 = exit delay only
2 = entry/exit 1
3 = entry/exit 2
4 = follows entry/exit
5 = has verification (resets
power upon event and when
code + OFF to clear condition. If
condition persists, zone
activates)
6 = resettable (upon code +
OFF)
[] to continue
Enter the desired zone attributes.
Note for Attribute 6:
If the resettable attribute is used, the Alm/Trbl Processing option
must be set to “0” for proper operation (see Alm/Trbl Proc prompt
below).
90 Bypass Option
0
Bypass Option
0 = zone type cannot be
bypassed
1 = auto bypassed when armed
in stay mode
[] to continue
Enter the desired bypass option.
90 Resp to Short
Armed 0 DArmd 0
Response to Shorts
0=none 2=trouble
1=Alarm 3=fault
[] to continue
Select the type of response when zones assigned to this zone type are
shorted when the system is armed.
NOTES: 1. For double-balanced zones, this entry must be 0.
2. For zone-doubled zones, both zones of the doubled pair
must be assigned the same response to a short.
90 Resp to open
Armed 0 DArmd 0
Response to Opens
0 = none 2 = trouble
1 = Alarm 3 = fault
[] to continue
Select the type of response when zones assigned to this zone type are
opened when the system is armed.
90 Vent Zone
0 = No, 1 = Yes
Vent Zone?
0=no
1=yes
[] to continue
If selected, the system can be armed even if zones assigned to this
zone type are faulted.
NOTE: After arming, faults on these zones will be ignored until the
zone is restored.
90 Alm/Trbl Proc
0
Alarm/Trouble
Processing
0=none
1=Zone type has automatic
restore
2=zone type uses Misc. Fault
Delay Time and automatic
restore
[] to continue
Select desired actions for zones assigned to this zone type.
Option 2: Select Miscellaneous Fault Delay in field *87.
90 TRBL SOUND
0
Trouble Sounding
0= none
1= one beep every minute
2= normal trouble sound (fast
beeps)
[] to continue
Select type of sounding upon trouble conditions on zones assigned to
this zone type.
90 ALARM SOUND
0
Alarm Sounding
0=none
1= keypad sound only
2= steady siren sounding
3= pulsing siren (temporal)
[] to continue
Select type of sounding upon alarm conditions on zones assigned to
this zone type.
90 Dial Delay
0=No, 1=Yes
Dial Delay?
0=no
1=yes
[] to continue
If selected, faults on zones assigned to this zone type will delay
reporting for whatever length of time that is selected in dial delay
(*50).