8 DACT-E3 Product Installation Document — P/N 9000-0581:J6 12/16/2019
Section 4: Formats and Codes
4.1 Formats
The DACT-E3 Digital Alarm Communicator Transmitter offers several formats that can be configured in CAMWorks. The DACT-
E3 uses the Ademco Contact ID format to transmit information to a Central Station. Table 4.1.1 lists the following DACT-E3
functions:
4.2 DACT-E3 Contact ID Event Reporting Codes in CAMWorks
In the CAMWorks program, there are two types of formats used to configure the DACT-E3 Contact ID Event Reporting Codes.
4.2.1 Standard Formats
The DACT-E3 can be configured to allow each SLC device to report an event by selecting the DACT Reporting Feature. To
define the Standard format for the ILI-E3/ILI95-E3 Series panel or SLP-E3 panel, enable the Standard Reporting Codes in
the DACT Report Format Section of the DACT Settings screen in CAMWorks. The Custom DACT Reporting Feature is
usually disabled by default. If you disable the Custom DACT Reporting Feature, the system uses the Standard Codes. For
information on the DACT-E3 Contact ID Event Reporting Codes for Standard Formats, refer to Table 4.2.1.1. Figure 4.2.1.1
illustrates an example of the DACT-E3 Contact ID Reporting Codes for Standard formats used to configure the following
types of systems.
Figure 4.2.1.1 Example of the DACT-E3 Contact ID Event Reporting Codes for Standard Formats
Function Description
Line seizure Takes control of the phone lines, disconnecting any premises phones using the same
lines.
Off/On-Hook Performs on and off-hook status to phone lines
Listen for dial tone - 440 Hz tone typical in most networks.
Dialing the Central Station phone number Programmable.
‘ACK’ and “Kiss-off” Tone Discern proper Central Station "ACK" and "Kiss-off" tone
Transmits data Transmit data to the Central Station.
Data verification Verify that data has been accepted by the Central Station
Phone line options Hang-up and release phone lines.
Communication Formats Communicate in a variety of formats
Table 4.1.1 DACT-E3 Functions
• Standard Format • Custom Format
STANDALONE SYSTEMS
CONTACT ID FORMAT
EXAMPLE
NOTE: Group Num bers are
truncated to range [00-99].
[1]=New Event
[3]=Restoral
Event Type
New Event
1
[R] [EEE] [00]
Fire Alarm
11 0 00
Not Used
Not Used
CONTACT ID FORMAT
Group
Number
Response
Type
Group 95
Smoke Alarm
SINGLE-RING
NETWORKED SYSTEMS
CONTACT ID FORMAT
EXAMPLE
1
Fire Alarm
11 0 00
New Event
CONTACT ID FORMAT
Node 25
MULTI-RING
NETWORKED SYSTEMS
CONTACT ID FORMAT
EXAMPLE
[1]=New Event
[3]=Restoral
Event Type
New Event
1
[R] [EEE] [0N]
Fire Alarm
11 0 01
Node
Number 100s
CONTACT ID FORMAT
Node
Number
10s & 1s
Response
Type
Node 103
[1]=New Event
[3]=Restoral
[R] [EEE] [00]
Event Type Node
Number
Response
Type
Not Used
Smoke Alarm
Smoke Alarm
NOTE: The 100s digit of the node
n u m b e r is re p o rted in the [O N ] field.
Not Used
[N N
T]
03 6
[N N
T]
[G G T ]
95
6
25