Table 4.2.1.1 lists the DACT-E3 Contact ID Event Reporting Codes for the Standard Formats.
Event SIA C o n t a ct I D 4/2 3 /1
(Standard DACT Reporting Formats)
Fire Alarm (Smoke or Manual Station)
FA [GGT]
1 110 [0G] [GGT] 0 [T] 0
Fire Alarm Restored
FH [GGT]
3 110 [0G] [GGT] 2 [T] 2
Waterflow Alarm Silenceable
FA [GGT] 1 110 [0G] [GGT] 0 [T] 0
Waterflow Alarm Non-Silenceable
SA [GGT] 1 113 [0G] [GGT] 0 [T] 0
Waterflow Alarm Restored Silenceable FH [GGT] 3 110 [0G] [GGT] 2 [T] 2
Waterflow Alarm Restored Non-Silenceable SH [GGT] 3 113 [0G] [GGT] 2 [T] 2
CO/Gas Alarm GA [GGT] 1 151 [0G] [GGT] 2 [T] 0
CO/Gas Alarm GH [GGT] 3 151 [0G] [GGT] 2 [T] 2
Trouble (except Waterflow or Special AMM/PID) FT [GGT] 1 373 [0G] [GG0] 8 [T] 8
Trouble Restored FJ [GGT] 3 373 [0G] [GG0] 7 [T] 7
Trouble (Waterflow AMM/PID) ST [GGT] 1 370 [0G] [GG0] 8 [T] 8
Trouble Restored (Waterflow AMM/PID) SJ [GGT] 3 203 [0G] [GG0] 7 [T] 7
Trouble (Special AMM/PID) UT [GGT] 1 370 [0G] [GG0] 8 [T] 8
Trouble Restored (Special AMM/PID) UJ [GGT] 3 370 [0G] [GG0] 7 [T] 7
Supervisory / Tamper (Module) SS [GGT] 1 203 [0G] [GGT] 6 [T] 6
Supervisory Restored (Module) SR [GGT] 3 203 [0G] [GGT] 7 [T] 7
PAS/Action/Supervisory (Sensor) FS [GGT] 1 200 [0G] [GGT] 6 [T] 6
PAS/Action/Supervisory Restored (Sensor) FR [GGT] 3 110 [0G] [GGT] 7 [T] 7
Disable (except Waterflow or Special AMM/PID) FB [GGT] 1 571 [0G] [GGT] 8 [T] 8
Disable Restored FU [GGT] 3 571 [0G] [GGT] 7 [T] 7
Disable (Waterflow AMM/PID) SB [GGT] 1 570 [0G] [GGT] 8 [T] 8
Disable Restored (Waterflow AMM/PID) SU [GGT] 3 570 [0G] [GGT] 7 [T] 7
Disable (Special AMM/PID) UB [GGT] 1 570 [0G] [GGT] 8 [T] 8
Disable Restored (Special AMM/PID) UU [GGT] 3 570 [0G] [GGT] 7 [T] 7
AC Fail AT 0 1 301 [0G] [000] 80 8
AC Fail Restored AR 0 3 301 [0G] [000] 70 7
Phone Line 1 Fault LT 1 1 351 [0G] [000] 81 8
Phone Line 1 Fault Restored LR 1 3 351 [0G] [000] 71 7
Phone Line 2 Fault LT 2 1 352 [0G] [000] 82 8
Phone Line 2 Fault Restored LR 2 3 352 [0G] [000] 72 7
Automatic Test (NORMAL) RP 0 1 602 [0G] [000] 90 9
Automatic Test (With Exception) RP 991 1 602 [0G] [991] 91 9
Begin Programming LB [GG3] 1 627 [0G] [GG3] 93 9
End Programming LX [GG3] 3 628 [0G] [GG3] 73 7
E3 Series Releasing (Standard DACT Reporting Formats)
Trouble (Releasing Device) (Supervisory) FS [GG3] 1 200 [0G] [GG3] 6 [3] 6
Trouble (Releasing Device) (Supervisory Restoral) FR [GG3] 3 200 [0G] [GG3] 7 [3] 7
Pre-Alarm (Action Supervisory) FS [GG3] 1 200 [0G] [GGZ] 6 [3] 6
Pre-Alarm (Action Restoral) FR [GG3] 3 200 [0G] [GGZ] 7 [3] 7
Pre-Release (Alarm) FA [GG1] 1 110 [0G] [GG1] 0 [1] 0
Pre-Release (Alarm Restoral) FR [GG1] 3 110 [0G] [GG1] 2 [1] 2
Release (Alarm) FA [GG1] 1 110 [0G] [GG1] 0 [1] 0
Release (Alarm Restoral) FR [GG1] 3 110 [0G] [GG1] 2 [1] 2
Abort (Supervisory) FS [GG3] 1 200 [0G] [GG3] 6 [3] 6
Abort (Supervisory Restoral) FR [GG3] 3 200 [0G] [GG3] 7 [3] 7
Manual Dump (Alarm) FA [GG1] 1 110 [0G] [GG1] 0 [1] 0
Manual Dump (Alarm Restoral) FR [GG1] 3 110 [0G] [GG1] 2 [1] 2
Table 4.2.1.1 DACT-E3 Contact ID Event Reporting Codes for Standard Formats