Configuration 
8/05  DC1010/1020/1030/1040 Product Manual  25 
Displays 
 Default Value 
Shown 
Parameter  Description 
SETSET
 
Main Control (OUT 1)  
Cycle of Control Output 
Output Type (SSR → 1, 4-20mA → 0, Relay → 10) 
Range: 0 to 150 seconds 
SETSET
 
Main Control (OUT 1)  
Actuation of Hysteresis 
For On/Off Control (P1=0) (Range 0-1000) 
ON:  PV<= (SP – HYS1) 
OFF:  PV> (SP + HYS1) 
SETSET
 
Sub Control (OUT 2) * 
P Value (Proportional Band) 
Same as P1 Configuration 
SETSET
 
Sub Control (OUT 2) * 
I Value (Integral Value) 
Same as I1 Configuration 
SETSETSET
 
Sub Control (OUT 2) * 
D Value (Derivative Time) 
Same as D1 Configuration 
SETSETSET
 
Sub Control (OUT 2) * 
Cycle of Control Output 
Same as CYT1 Configuration 
SETSETSET
 
Sub Control (OUT 2) * 
Actuation of Hysteresis 
Same as HYS1 Configuration 
SETSET
 
Main Control (OUT 1) 
Gap 
Control Output is turned off before reaching setpoint 
Turning Point = SP – GAP 1; Off = (OUT 1 = Heat) 
SETSET
 
Sub Control (OUT 2) * 
Gap 
Control Output is turned off before reaching setpoint 
Turning Point = SP + GAP 2; On = (OUT 2 = Cool) 
SETSET
 
Function Lock  Refer to Section 4.4 for Mode access designations. 
* Will only appear in models with “OUT2” option.