Configuration 
8/05  DC1010/1020/1030/1040 Product Manual  29 
4.3 ALARMS CONFIGURATION 
4.3.1  Alarm Function Selections 
These Alarm Function Selections are entered in “Configuration 2”. See Section 4.2.1. 
Table 4-3 Alarm Function Selections 
Code  Description  Hold-ON  Refer to 
00 / 10 
None      
01 
Deviation high alarm  YES  Figure 4-2 
11 
Deviation high alarm  NO  Figure 4-3 
02 
Deviation low alarm  YES  Figure 4-4 
12 
Deviation low alarm  NO  Figure 4-5 
03 
Deviation high / low alarm  YES  Figure 4-6 
13 
Deviation high / low alarm  NO  Figure 4-7 
04 / 14 
Band alarm  NO  Figure 4-8 
Figure 4-9 
05 
Absolute value high alarm  YES  Figure 4-11 
15 
Absolute value high alarm  NO  Figure 4-12 
06 
Absolute value low alarm  YES  Figure 4-13 
16 
Absolute value low alarm  NO  Figure 4-14 
07 
Segment end alarm  
(Use for program model only) 
- Paragraph 
4.3.4.1 
17 
Program run alarm 
(Use for program model only) 
- Figure 4-15 
08 
System error alarm (On)  -  Figure 4-16 
18 
System error alarm (Off)  -  Figure 4-17 
19 
Soak timer  -  Paragraph 
4.3.5.3 
“Hold-On”(Blocking) means that the alarm does not work at the first time. The alarm 
signal is suppressed until the parameter gets to the non-alarm limit or band.