Configuration 
8/05  DC1010/1020/1030/1040 Product Manual  27 
Displays 
Default Value 
shown except for 
examples 
Parameter  Description 
SETSET
 
Time set for Alarm 2 
 
* Range: 0-99 min, 59 seconds 
0= flickering alarm, 99:59= continual alarm 
Other = Time delay for alarm 
SETSET
 
Alarm Code for Alarm 3 
* Refer to Table 4-3 for Alarm Codes. 
SETSET
 
Time set for Alarm 3 
 
* Range: 0-99 min, 59 seconds 
0= flickering alarm, 99:59= continual alarm 
Other = Time delay for alarm 
SETSET
 
Hysteresis for alarms 
Sets the hysteresis for alarm actuation  
(Range=0 to 1000) 
ON: PV<=(SPHYS1) 
OFF: PV>(SP+HYS1) 
example 
SETSET
 
Main Control (OUT1) **0 
Lower Limit of linear output 
Used to adjust the linear control output during calibration
* DO NOT change the value without technical assistance
example 
SETSET
 
Main Control (OUT1) ** 
Upper Limit of linear output 
Used to adjust the linear control output during calibration
* DO NOT change the value without technical assistance
example 
SETSET
 
Sub Control (OUT2) ** 
Lower Limit of linear output 
Used to adjust the linear control output during calibration
* DO NOT change the value without technical assistance
example 
SETSET
 
Sub Control (OUT2) ** 
Upper Limit of linear output 
Used to adjust the linear control output during calibration
* DO NOT change the value without technical assistance
example 
SETSET
 
Auxiliary Output 
Lower Limit of Aux. output 
Used to adjust the linear control output during calibration
* DO NOT change the value without technical assistance
example 
SETSET
 
Auxiliary Output 
Upper Limit of Aux. output 
Used to adjust the linear control output during calibration
* DO NOT change the value without technical assistance
SETSET
 
Motor Time 
Three Position Step Control - This is the time it takes the 
motor to travel from 0 to 100% (fully closed to fully 
open).  This time can usually be found on the nameplate 
of the motor. 
Range: 5 – 200 seconds