HONEYWELL EMERGENCY NOTIFICATION MANAGER
39-00008-1
14
VeriFire Tools:
Leave the Display and Control Center box unchecked in the
XLS3000 and XLS-NCA2. Do not enable DCC.
Fig. 10. VeriFire Tools, XLS3000/XLS-NCA2
XLS140-2/XLS120
Panel: In the Utility Program Menu:
Set "DCC-mode" to "N" (no) to disable DCC participation.
Fig. 11. Utility Program, XLS140-2/XLS120
VeriFire Tools:
In the General II screen:
Fig. 12. VeriFire Tools, XLS140-2/XLS120
Leave the Display and Control Center box unchecked in the
XLS140-2 and XLS120 service.
Local Control
When the XLS3000 in network display mode, or the XLS-
NCA2, is acting as a subsidiary device (that is, it is not part of
an ACU, LOC or CCS), its local control setting must be
disabled.
Panel:
Set Local Mode to NO.
Fig. 13. Panel Settings Screen, XLS3000/XLS-NCA2
VeriFire Tools:
Leave the Local Control box unchecked.
Fig. 14. VeriFire Tools, XLS3000/XLS-NCA2