HONEYWELL EMERGENCY NOTIFICATION MANAGER
39-00008-1
22
Fire Active Tone
When Fire is the highest priority in a system, an XLS-DVC
must be programmed in VeriFire Tools to generate a "Fire
Active Tone". This programming is required for two reasons:
1. It generates an audible reminder every 30 seconds that
Fire has control of the system and that MN signals may
be suppressed.
2. It suppresses MN sequences and pages that come
below it in priority, until a fire reset clears the "MN Active
Tone".
NOTE: MN or OTHER sequences and pages will not be
suppressed for fire alarms without the Fire
Active Tone, properly prioritized in the PAM.
In the Audio Message Prog. Service of VeriFire Tools DVC
programming, build the Fire Active Tone audio sequence on
the Message Sequences tab.
Fig. 29. Creating a Fire Active Tone Sequence
In the Audio Message Prog. Service Input programming, assign the Fire Category to the Fire Active Tone sequence, and give it
the priority just below the Fire Category inputs.