Fire Alarm Control Panel IQ8Control C / M
FB 798951.10.GB0 / 04.15 57
6.4.2 Connecting master box (Relay K1)
Relay K1 for the connection of a master box is part of the peripheral module.
The control configuration of relay K1 can be set to
monitored and switching the positive potential
switching the positive potential
or as a non-monitored change-over contact
by means of jumpers.
BR 8
BR 7
BR 6
BACK
BR1BR2
K1
CNCNO
K1
GND
1
2
3
Fig. 48: Location of the master box relay K1 and the jumpers BR 6 to 8 on the Field device module
Setting the operating mode for relay K1
Jumpers Function
BR 1
Activation of master box relay (K1) also in the event of a fire alarm with the control panel in
the CPU failure mode (factory setting)
BR 1
No activation of the master box relay (K1) in the event of CPU failure-fire
BR 2
No activation of the master box relay (K1) in the event of a fire alarm when the cover
contact on the control panel housing is open (factory setting)
BR 2
Activation of master box relay (K1) even with cover contact open (outer housing)