Fire Alarm Control Panel IQ8Control C / M
84 FB 798951.10.GB0 / 04.15
8.2 4- Relay module
This micro module accommodates four freely programmable, non-monitorable, potential-free relays for activating
external devices and system components.
Relay assignment is programmed with the service PC and programming software tools 8000. For each relay,
you may enter a specific additional text comprising 25 characters per line for output on the display and protocol
printer.
X1
K 3K 2K 1
S 2
K 4
S 4 S 3
F 4
S 1
F 1F 2F 3
Example of switch position
NO contact NC contact
n.o.
4-relay module
n.c.
Fig. 73: 4- Relay module
X 1
64-way plug connector to micro module slot of the Basic module, Field device module or
Extension module
K1 to K4
freely programmable, potential-free relay contacts (max. contact rating max. 30 V DC/ 1 A).
S1 to S4
Switch for setting the NC or NO contact function for each relay.
F1 to F4
Electronic fuse (multifuse): to reset, de-energise for approx. 30 seconds at the relevant screw
terminals on the terminal card.
No AC voltages may be applied to the relays built-into the Fire Alarm Control Panel. This applies
also to those relays operated in the >non-monitored< mode.