EXCEL 500/600 INSTALLATION INSTRUCTIONS
XF525A Three-Position Output Module
Technical Specifications
An L 16 miniature circuit breaker or G 10 A quick blow fuse
should be used to protect the 240 Vac mains supply.
Voltage rating:
240 Vac or 28 Vdc max.
NOTE: The maximum voltage for the U.S. is 24 V.
Current rating:
0.2A max. at 240 Vac
1.2A max. at 28 Vdc
Fig. 65. XF525A Three-position output module
31 EN1R-1047GE51 R0902