EasyManua.ls Logo

Honeywell FS20X Series - LED Status Indicators; Normal Operation

Honeywell FS20X Series
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
34
FS20X Fire and Flame Detectors
LED Status Indicators
The detector status is indicated by three LEDs:
Green
blinking (flashing) once every ten seconds indicates a normal, safe operational
condition (i.e., no faults or alarms).
off when no external input power is applied to the detector.
Yellow
blinking (flashing) when the window is dirty
on steadily for all other fault conditions
“Red flashes while FirePic is being stored”New Bullet:
“Red turns on when a fire is alarmed”
Normal Operation
In normal operation
1
the green LED, shown in Figure 27, blinks every ten seconds. If
one of the 4-20 mA options is selected (see “SW1 Configuration” on page 31), the
current, sink, or source will be 4.0 mA ±0.6 mA. Only the current source mode has
been certified to the EN54-10 standard.
Figure 27. Green LED location
1 Normal operation is dened as the detector with 24 VDC applied without alarm or fault conditions.