EasyManua.ls Logo

Honeywell Gamewell 7100 Series - Notification Appliance Circuits; Circuit Ratings and Wiring; Signaling Line Circuits; Style 4 and Style 7 Wiring

Honeywell Gamewell 7100 Series
50 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9000-0447 Rev. I
Page 15 of 42
3.3 Notification Appliance Circuits
The 7100 provides two (2), 24 VDC Class B, Style Y
notification appliance circuits. Class A, Style Z operation is
accomplished by adding the Class A Option (CAOM) Module.
Wiring Instructions
NAC 1 - TB1-1 (+), TB1-2 ( - )
NAC 2 - TB1-3 (+), TB1-4 ( - )
(Polarity markings indicate the polarity of the circuit in
alarm condition).
Use U.L. Listed End of Line Resistor EOL-N (47K),
P/N 4700-0512
Circuit Ratings
24 VDC regulated
Max. alarm load 1.5 amp./circuit
Ground fault test impedance: 20 kOhms
18 AWG minimum
If synchronization of strobes is required
MDL-FC Synchronization Modules must be connected.
Class B, Style Y operation only
Special application: See Compatibility Addendum/
P/N 9000-0427 for a list of Gamewell-FCI Approved, UL Listed notification appliances.
Supervised
Power-limited
NOTE: The CAOM module is furnished with the End of Line resistor installed.
3.4 Signaling Line Circuits
The 7100 provides one (1), or two (2), 24 VDC Class B,
Style 4 signaling line circuits. Class A, Style 6 or 7
operation is accomplished by adding the Class A Option
(CAOM) Module. See Figure 7 for Style 4 or 6 wiring, and
Figure 8 for Style 7 wiring.
Wiring Instructions
SLC 1 - TB3-1 (+), TB3-2 ( - )
SLC 2 - TB3-3 (+), TB3-4 ( - ) (7100-2 only)
(Polarity markings indicate the polarity that should
be maintained throughout the circuit. Polarity must be
observed on all devices connected to the circuit).
Circuit Ratings
24 VDC (nominal)
Current: 0.090 amp max. (supervisory)
0.097 amp max. (alarm)
0.750 amp max. (short circuit)
40 Ohms max. line resistance
0.5 µf max. line capacitance
Ground fault test impedance: 20 kOhms
18 AWG minimum, straight lay or twisted-pair
unshielded
Power-Limited
Supervised
See Compatibility Addendum/ P/N 9000-0427 for a list of Gamewell-FCI Approved, UL
Listed sensors and modules.
Figure 6 Notification
Appliance
Circuit Wiring
NOTE: A white wire lead of The NCM-1
module (if used) must be connected to earth
ground.
Figure 7 Signaling Line Circuit Wiring

Table of Contents

Related product manuals