EasyManua.ls Logo

Honeywell Gamewell 7100 Series - Table 5-2 Sensor Sensitivity Settings

Honeywell Gamewell 7100 Series
50 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9000-0447 Rev. I
Page 29 of 42
[SET ] 1: Verification 2: Sensitivity
[DEFAULTS] 3: PAS 4: Multilevel
1: Opens Set Default Verify Options Menu.
2: Opens Set Default Sensitivity Menu.
3: Opens Set PAS Parameters Menu.
Main
Config
Global
Device defaults
4: Opens Set Multilevel Parameters Menu.
[DFLT ] 1: Dflt Ion, Photo Verify (None)
[VERIFY] 2: Dflt Manual Sta Verify (None)
1: Scrolls through None, Smoke, PAS.
Main
Global
ConfigDevice defaults
Default Verification
2: Toggles between None and PAS.
[DFLT] DAY 1: Photo (Low) 2: Ion (Low)
[SENS] NIT 3: Photo (Med.) 4: Ion (Med.)
1: Scrolls through selections for photo sensor daytime
sensitivity.
2: As above for Ion.
3: As above for photo night time sensitivity.
Main
Config
Global
Device Defaults
Default Sensitivity
4: As above for Ion.
[PAS ] 1: Night Bypass (ON)
[OPTION] T1 (15sec) T2 (180sec)
1: Toggles Night Bypass ON/OFF.
Main
Config
Global
Device Defaults
PAS Parameters
T1 and T2 parameters are fixed in firmware; they are shown
for reference only.
[MULTI] 1: Alert Threshold (35%)
[LEVEL] 2: Action Threshold (65%)
1: Scrolls through Alert Threshold options (20, 35, 50, 65%)
2: Scrolls through Action Threshold options (35, 50, 65, 80%)
Main
Config
Global
Device defaults
Multilevel Params
OK: accepts settings as shown (if valid)
[NAC ] 1:Delay Times
[OPTIONS] 2: Coding & Silencing
1: Opens Set NAC Delays Menu.
Main
Config
Global
NACs
2: Opens Set NAC Coding Menu.
[NAC ] 1: Silence Inhibit (None)
[DELY] 2: Cutoff (None)
1: Scrolls through Silence Inhibit Delay options (None, 1 min,
3 min, 5 min)
Main
Config
Global
NACs
Delay Times
2: Scrolls through Signal Cutoff Delay options (None, 5 min,
10 min, 15 min)
[NAC ] NAC 1 1: (Coded) 3: (Silenceable)
[MISC] NAC 2 2: (Steady) 4: (Nonsilenceable)
1: Toggles NAC 1 between Coded and Steady.
2: Toggles NAC 2 between Coded and Steady.
3: Toggles NAC 1 between Silenceable and Non-silenceable.
Main
Config
Global
NACs
Coding
4: Toggles NAC 2 between Silenceable and Non-silenceable.
Table 5-2 Sensor Sensitivity Settings
Photo Ion
Low 2.0 1.3
L/M 1.75 1.2
Med. 1.5 1.0
M/H 1.25 0.88
High 1.0 0.77