9000-0447 Rev. I 
 
  ii 
reduced terminal contact pressure and difficulty 
with screw terminal removal. Disconnect all 
sources of power before servicing, removing, or 
inserting any circuit boards. Control unit and 
associated equipment may be damaged by 
removing and/or inserting cards, sub-assemblies, 
or interconnecting cables while the unit is 
energized
. 
WIRING CONSIDERATIONS: 
This fire alarm control panel contains power-
limited circuits. You cannot connect external 
sources of power to these circuits without 
invalidating their approval. 
Verify that wire sizes are adequate for all 
initiating device and notification appliance 
circuits. Most devices cannot tolerate more than 
a 10% drop from the specified device voltage. 
The installer must make sure that the wiring and 
devices installed in the system meet the current 
National Electrical Code, NFPA 70, and all 
applicable state and local building code 
requirements. 
Use the conductor size and type required by local 
codes. (See NFPA 70, Article 760). Wiring 
resistance must not be more than that shown on 
the field wiring diagrams. 
To reduce errors and help in servicing the 
system, all conductors should be tagged or 
otherwise coded and logged at installation to 
identify circuit assignment and polarity. If the 
conductors are logged with a code, keep the log 
that explains the code with the manual, so that it 
is available to other people working on the panel. 
Like all solid state electronic devices, this system 
may operate erratically or be damaged when 
subjected to lightening induced transients. 
Although no system is completely immune to 
lightening transients and interference, proper 
grounding will reduce susceptibility. We do not 
recommend the use of overhead or outside aerial 
wiring due to the increased susceptibility to 
nearby lightening strikes. Consult with the 
Gamewell-FCI Technical Support Department if 
any problems are anticipated or encountered. 
To prevent the spread of fire, use proper patching 
materials to areas where system wiring passes 
through the fire-rated walls or floors. 
 
SURVIVABILITY: 
Per the National Fire Alarm Code, NFPA 72, all 
circuits necessary for the operation of the 
notification appliances shall be protected until 
they enter the evacuation signaling zone that 
they serve. Any of the following methods shall be 
considered acceptable as meeting these 
requirements: 
1)  A 2-hour rated cable or cable system 
2)  A 2-hour rated enclosure 
3) Performance alternatives approved by 
Authority Having Jurisdiction 
 
MAINTENANCE: 
To keep your fire alarm system in excellent 
working order, ongoing maintenance is required 
per the manufacturer’s recommendations and UL 
and NFPA Standards, and applicable state and 
local codes. At a minimum, the requirements of 
Chapter 7 of NFPA, the National Fire Alarm 
Code, shall be followed. A preventative 
maintenance agreement should be arranged 
through the manufacturer’s local representative. 
Though smoke detectors are designed for long 
life, they may fail at any time. Any smoke 
detector, fire alarm system, or any component of 
that system shall be repaired or replaced 
immediately. 
OTHER CONSIDERATIONS: 
The equipment was tested according to EC 
directive 89/336/EEC for Class A equipment and 
was verified to the limits and methods of EN 
55022. 
An automatic fire alarm system—typically 
made up of smoke detectors, heat detectors, 
manual pull stations, audible warning devices, 
and a fire alarm control panel with remote 
notification capability can provide early warning 
of a developing fire. Such a system, however, 
does not assure protection against property 
damage or loss of life resulting from a fire. 
The Manufacturer recommends that smoke 
and/or heat detectors be located throughout a 
protected premise following the  
recommendations of the current edition of the 
National Fire Protection Association NFPA 
Standard 72, manufacturer’s recommendations, 
State and local codes. A study by the Federal 
Emergency Management Agency (an agency of 
the United States government) indicated that 
smoke detectors may not into alarm in as many 
as 35% of all fires. While fire alarm systems are 
designed to provide early warning against fire, 
they do not guarantee warning or protection 
against fire. A fire alarm system may not provide 
timely or adequate warning, or simply may not 
function, for a variety of reasons:  
Smoke detectors may not sense fire where 
smoke cannot reach the detectors such as in 
chimneys, in or behind walls, on roofs, or on the 
other side of closed doors. Smoke detectors also 
may not sense a fire on another level or floor of a 
building. A second-floor detector, for example, 
may not sense a first-floor or basement fire. 
Particles of combustion or “smoke” from a 
developing fire may not reach the sensing 
chambers of smoke detectors because: 
•  Barriers such as closed or partially closed 
doors, walls, or chimneys may inhibit particle or 
smoke flow.   
•  Smoke particles may become “cold,” stratify, 
and not reach the ceiling or upper walls where 
detectors are located.