9000-0447 Rev. I
Page 32 of 42
[CONFIG] 1: Type 2: General Resp 3: Groups
[L,AAA ] 5: Location 6: View 7: Copy L,AAA
1: Opens Set Output Type Menu.
2: Opens Assign Output To Group(s) Menu.
3,4: Unused.
5: Opens Set SLC Device Location Menu.
6: Displays all settings for this device.
Main
Config
Outputs
Select
7: Copies settings of the specified device (last output modified).
[L,AAA] 34 Silenceable Signal AOM
Key in Output Type# or use <,>
Main
Config
Outputs
Select
Type
<>: scroll through types which match this physical device # keys:
Enter type number (no restrictions: see Type Table)
Output device types cannot be edited.
If the new type is an input device, “OK” key returns to the System
Config Menu, otherwise to Output Config.
[L,AAA] Activates for Day Alarm (YES)
[GNL RSP] select condition 1: YES/NO
1: Toggles specified general group membership YES/NO.
Select
General Response
[L,AAA] Group 1: 36 (00 = none)
[GROUPS] Key in group # <,> change
<>: scrolls through list of general groups.
Select
I/O Group
Number keys: set group number.
[L, 1AA] Slncbl NAC Main Lobby
ALd ALn ACT SPV TOR WKT TBL 02 00 00
<>: select which of the three possible groups to set.
Select
View
Shows: SLC and Address, Type, Location, General responses,
Group membership. General responses show above abbreviations.
[SELECT] Group number: 03
[GROUP ] Key in group# or use <,>
If the output is activated in that condition, or – if not.
# keys: enters group number.
Main
Config
Groups
<>: Scrolls up or down to next group.
[GROUP] Activates General Alarm (NO)
[ 03 ] Activates Genrl Supervisory (YES)
OK: Accepts group number, opens Configure Group Menu.
1: Toggles General Alarm response on/off (applies to alarms
initiated by Alarm, Manual, Waterflow, and Aux devices, for both Day
and Night general alarm).
2: Toggles General Supervisory response on/off (applies to off-
normals initiated by Supervisory and Tamper devices).
Main
Config
Groups
Select
General
Response
If a group contains inputs of several types (an unusual case), the
appropriate general flag is applied for each new alarm/off-normal.