EasyManua.ls Logo

Honeywell HPF-PS10E - Appendix B: Application Examples; B.1: Controlling Nacs for Selective Silence Operation Using a Control Module

Honeywell HPF-PS10E
52 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix B: Application Examples
B.1 Controlling NACs For Selective Silence Operation Using a Control Module
In this application, the power supply has been set as a master with synchronized outputs and selective silence (see DIP switch settings and
Selective Silence Operation information in Section 3). This application requires Input #1 to be controlled by the FACP. Input #2 is required
for controlling selective silence via a control/relay module, programmed as an alarm output and a silenceable point. Only Mass Notification,
Fire, or combo Mass Notification/Fire NACs are allowed in this configuration. The control module can be powered by one of the HPF-PS
output circuits, configured as aux power (24VDC).
The following notes apply to Figure B.1.
When the HPF-PS power supply is in an inactive state (FACP NAC not active), a trouble on the NAC circuit will result in an open circuit
condition on the FACP (monitored by End-of-Line Resistor across TB5, Terminals 1 and 4). As an alternative, the trouble contacts at TB1 of
the power supply can also be used for limited trouble monitoring excluding Selective Silence output faults. Refer to Section 5 for more infor-
mation.
Refer to Section 3 for instructions on setting the DIP switches.
Selective Silence output faults are only reported via Command Input #1 (not Command Input #2).
Wire NACs as shown on page 14.
Do not loop wires under screw terminals. Break wires to maintain proper supervision.
An End-of-Line Resistor must be installed across all input circuits, Terminals 1 and 4, for control module wiring supervision (the ELR
value is dependent on the module/FACP employed).
For a list of compatible devices, refer to the HPP Device Compatibility Document #54399.
Refer to the SLC Wiring Manual for more information.
NO NC CNONC C
TB4
TB15
T
B
2
T
B
1
T
B
1
3
T
B
1
2
T
B
1
1
T
B
1
0
T
B
9
T
B
8
T1
T11
T2
T10
T3
T9
T4
T8
T5
T7
T6
A- B+ B- A+ A- B+
B
-
A
+
A
-
B
+
B
-
A
+
Figure B.1 Controlling Multiple Outputs with One Input
Control Module*
SLC
*If the SLC device does not match
the one in this figure, refer to the
SLC manual wiring conversion
charts for legacy and newer ver-
sions of the modules.
NAC Output Circuits
24VDC power output
NAC
FACP
HPF-PS Series Instruction Manual — P/N LS10227-003HP-E:C 2/2/2022
43

Table of Contents

Related product manuals