INNCOM E7 THERMOSTAT USER GUIDE
36-00013—02 12
Thermostat Initialization
Power up for the first time puts the e7 thermostat into Initialization Mode. This mode provides the contractor or
electrician with a simple setup for the thermostat to control the intended HVAC equipment before normal use.
Under normal operating conditions, the e7 thermostat is designed to provide energy management and operates the
HVAC equipment using stand-alone energy management configurations. These configurations are intended to utilize a
wired door switch and the e7's on-board motion sensor for occupancy detection logic.
Initialization Mode configuration default parameters are outlined in the following tables.
Default HVAC Unit Control
*All default values are adjustable with the INNtool and engINN software configuration tools.
Function Default Value*
Comfort Control
Guest Selectable Temperature Control Limits (rented/Occupied) - Low 65 F
Guest Selectable Temperature Control Limits (rented/Occupied) - High 80 F
LEM Guest Selectable Temperature Control Limits (rented / occupied) - Low 60 F
LEM Guest Selectable Temperature Control Limits (rented / occupied) - High 85 F
Check-in temperature 72 F
Default Thermostat Dormant Mode Display Set Point
Energy Conservation
Rented Room - Temperature Clipping Heating 85 F
Rented Room - Temperature Clipping Cooling 55 F
Occupied Mode Temperature Control Delta 1 F
Rented / Unoccupied Setback Temperature Variance (Delta from Guest-
selected Temperature Setting)
4 F
HVAC Equipment Operation
Latent Heat Blowout 45 seconds
Latent Cool Blowout 45 seconds
Fan Operation When Temperature is Satisfied (Occupied Room) Fan Off
Fan operation Unoccupied / Satisfied Fan Off
Fan operation Unoccupied /HVAC Off Fan off
Exposure
Time Delay for Balcony Door Exposure 30 seconds
Disable Fan Operate as satisfied
Disable Cooling Apply cool at danger high
Disable Heating Apply heat at danger low