INNCOM E7 THERMOSTAT USER GUIDE
36-00013—02 14
2 FAN SPEED HEAT PUMP, REVERSING VALVE POSITION DETERMINES HEATING OR
COOLING
4-PIPE, 3-SPEED FAN FCU WITH HOT AND COLD WATER AVAILABLE
2-PIPE, 2-SPEED FAN FCU WITH COLD WATER IN PIPE, HEAT STRIP, AND CONTINUOUS
FAN SPECIFIED
System State
(Off / Auto)
Room
Temperature Set Temperature Fan Reversing Valve Compressor
Off 75 degrees 72 degrees OFF Cool Position OFF
AUTO 72 degrees 72 degrees OFF Cool Position OFF
AUTO 73 degrees 72 degrees LOW Cool Position OFF
AUTO 75 degrees 72 degrees MED Cool Position ON
AUTO 77 degrees 72 degrees HIGH Cool Position ON
AUTO 70 degrees 72 degrees OFF Heat Position ON
System State
(Off / Auto)
Room
Temperature Set Temperature Fan
Cold Water
Valve Hot Water Valve
Off 75 degrees 72 degrees OFF CLOSED CLOSED
AUTO 72 degrees 72 degrees OFF CLOSED CLOSED
AUTO 73 degrees 72 degrees LO OPEN CLOSED
AUTO 75 degrees 72 degrees MED OPEN CLOSED
AUTO 77 degrees 72 degrees HIGH OPEN CLOSED
AUTO 67 degrees 72 degrees LOW CLOSED OPEN
AUTO 67 degrees 72 degrees HI CLOSED OPEN
System State
(Off / Auto)
Room
Temperature Set Temperature Fan
Cold Water
Valve Hot Water Valve
Off 75 degrees 72 degrees LOW CLOSED OFF
AUTO 72 degrees 72 degrees LOW CLOSED OFF
AUTO 73 degrees 72 degrees LOW OPEN OFF
AUTO 75 degrees 72 degrees HIGH OPEN OFF
AUTO 77 degrees 72 degrees HIGH OPEN OFF
AUTO 67 degrees 72 degrees LOW CLOSED OFF
AUTO 67 degrees 72 degrees HI CLOSED ON