Parameters
10.10.4 Function of terminal 66
Parameter 71
Parameter 71 = 0: Off.
Parameter 71 = 8: AND with input at terminal 46 (emer-
gency stop).
Parameter 71 = 20: LDS ignition position check.
The BCU does not perform a burner start-up, restart or
start-up attempt until the buttery valve is in ignition
position. To ensure that the burners only start with the
start-up fuel rate, the FCU issues an enable signal to
start the burner via terminal 66 to the BCU with setting
P71 = 20. In addition, the safety interlocks must have
been enabled by the FCU.
B
CU
B
CU
FCU
µC
5
4
55
53
+24V
M
L1
L1
54 55
53
M
66 66
10.10.5 Function of terminal 67
Parameter 72
Parameter 72 = 0: Off.
Parameter 72 = 8: AND with input at terminal 46 (emer-
gency stop).
10.10.6 Function of terminal 68
Parameter 73
Parameter 73 = 0: Off.
Parameter 73 = 8: AND with input at terminal 46 (emer-
gency stop).