EasyManua.ls Logo

Honeywell Krom Schroder BCU 580 - 16.5 Safety-specific characteristic values

Honeywell Krom Schroder BCU 580
131 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
BCU 580 · Edition 11.15l 123
Technical data
16.5 Safety-specific characteristic values
Suitable for Safety Integrity Level Up to SIL 3
Diagnostic coverage DC 97.2 %
Type of subsystem Type B to EN 615082:2010
Operating mode
High demand mode pursuant to EN
615084:2010
Mean probability of dangerous failure
PFH
D
11.5 x 10
9
1/h on BCU 580..F1
11.5 x 10
9
1/h on BCU 580..F2
14.5 x 10
9
1/h on BCU 580..F3
Mean time to dangerous failure
MTTF
d
MTTF
d
= 1/PFH
D
Safe failure fraction SFF 99.4 %
Mean probability of dangerous failure PFH
D
of
individual safety functions
Valve proving system 5.5 x 10
9
1/h
Safety interlocks 5.5 x 10
9
1/h
Emergency stop with optional input 5.4 x 10
9
1/h
Air flow monitoring 7.2 x 10
9
1/h
Air flow monitoring with optional input 7.1 x 10
9
1/h
Flame control 6.5 x 10
9
1/h
Approaching position for ignition capacity with F1/IC 20 5.6 x 10
9
1/h
Approaching position for ignition capacity with F2/RBW 5.9 x 10
9
1/h
Approaching position for ignition capacity with F3 5.3 x 10
9
1/h
SIL 3 is only achieved in conjunction with actuators
IC 20 or RBW if a separate gas valve is used to limit the
pilot gas rate, see page 65 (Burner application), pa-
rameter 78 = 3.
Relationship between the Performance Level (PL)
and the Safety Integrity Level (SIL)
PL SIL
a
b 1
c 1
d 2
e 3
Pursuant to EN ISO 138491:2006, Table 4, the BCU
can be used up to PL e.
Max. service life under operating conditions:
20 years after date of production.
For a glossary of terms, see page 127 (Glossary).
For further information on SIL/PL, see www.k-sil.de

Table of Contents