Technical data
16 Technical data
16.1 Electrical data
Mains voltage
BCU..Q: 120 V AC, 15/+10%, 50/60 Hz, ±5%,
BCU..W: 230 V AC, 15/+10%, 50/60 Hz, ±5%,
for grounded or ungrounded mains.
Power consumption
At 230 V AC approx. 6 W/11 VA plus power consump-
tion per AC input of approx. 0.15 W/0.4 VA,
at 120 V AC approx. 3 W/5.5 VA plus power consump-
tion per AC input of approx. 0.08 W/0.2 VA.
Flame control
With UV sensor or ionization sensor,
for continuous operation (intermittent operation with
UVS).
Flame signal current: ionization control: 2–25 μA,
UV control: 5–25 μA.
Signal cable for flame signal current: max. 100 m
(164 ft).
Contact rating
Valve outputs V1, V2, V3 and V4 (terminals 13, 14, 15
and 57):
max. 1 A each, cos ϕ ≥ 0.6.
Actuator outputs (terminals 53, 54 and 55):
max. 1 A each, cos ϕ = 1.
Ignition transformer (terminal 9):
max. 2 A.
Total current for the simultaneous activation of the
valve outputs (terminals 13, 14, 15 and 57), the actu-
ator (terminals 53 – 56) and the ignition transformer:
max. 2.5 A.
Signalling contact for operating and fault signals:
max. 1 A (external fuse required).
Number of operating cycles
The fail-safe valve outputs V1, V2, V3 and V4 are moni-
tored for correct functioning and are thus not subject to
a max. number of operating cycles.
Actuator (terminals 53, 54 and 55): max. 1,000,000,
signalling contact for operating signals: max.
1,000,000,
signalling contact for fault signals: max. 10,000,
On/Off button: max. 10,000,
Reset/Information button: max. 10,000.
Input voltage of signal inputs:
Rated value 120 V AC 230 V AC
Signal “1 80–132 V 160–253 V
Signal “0” 0–20 V 0–40 V
Signal input current:
Signal “1 max. 5 mA
Fuses, replaceable,
F1: T 3,15A H,
F2: T 2A H, pursuant to IEC 601272/5.