BCU 580 · Edition 11.15l 91
Parameters
Parameter 75 = 2: MIN. to MAX. capacity; standby in
CLOSED position. The control range while the burner
is operating is between the positions for minimum ca-
pacity (S2) and maximum capacity (S3). The burner is
ignited in the position for ignition capacity (S1). When
the burner is switched off, the actuator is moved to the
closed position (S4).
This operating mode can be achieved with an actua-
tor IC 20 or alternatively with a comparable three-point
step actuator.
If the air supply is stopped on a heated furnace with
the burner switched off, the controls are protected
from the hot furnace atmosphere as a result of the
buttery valve being in the closed position (limited
by S4). Check whether the burner can cope without
cooling in this situation.
IC 20
Switching cam setting for ignition capacity, minimum and maximum capacity
as well as pre-purge and standby:
S1: for ignition capacity of the burner.
S2: for minimum capacity of the burner.
S3: for maximum capacity of the burner and pre-purge.
S4: for the closed position of the butterfly valve and standby.
90°
S4
S2
S1 S3
Burner control range
CLOSED
Butterfly valve setting range
Control range
Move to ignition position
Ignition pos.
Max. pos.
OPEN
S4
S2
Min.
pos.
Closed
pos.
MIN
MIN
MAX
MAX
PE
L1
N
3 2 116 67 4812 1115 13
S3 S4
S11
S10
90°
M
IC 20
PE
S1S2
90°
90°
S1
Min Max
Y-
Y+
53 54 55 56
52
1 2 3 4645
65 66 67 68
49 50 51
17 18 37 38
13 14 15
BCU 580..F1
3,15AT
µC
88
c
c
41 42
24V
DC
5 6 9 11 1210762 61