Programming
92 MS-5UD/MS-10UD Series PN 52626:B 8/01/2008
The following table lists the Zone Alarm Types that can be programmed for zones 1 through 10
and the corresponding Event Codes for Ademco Contact ID and SIA DCS Formats. Note that
Table 3.3 on page 93, Table 3.4 on page 94, Table 3.5 on page 95 and Table 3.6 on page 97 list
the default settings for Zone 1 through Zone 10. These can be changed to any of the Types
listed in Table 3.2 .
Note: The third character in the SIA-DCS Format (x in the table below) represents the zone
number.
The following tables list all of the Events and their default Event Codes for the Ademco Contact
ID and SIA-DCS Communication Formats.
Note: A detector freeze condition will be reported as a Supervisory Event Code.
Table 3.2 Zone Alarm Type Event Codes
Zone Alarm Type Ademco Contact ID SIA-DCS Format
Active Active Restoral
Pull-Station 115 FAx FHx
Waterflow 113 SAx SHx
Waterflow Nonsilenceable 113 SAx SHx
Combo 113 SAx SHx
Combo AutoResettable Supervisory 113 SAx SHx
2-Wire Detector 111 FAx FHx
Normally Open Contact 110 UAx UHx
Fire 110 FAx FHx
Tamper 144 TAx THx
Supervisory 200 FSx FVx
Supervisory AutoResettable 200 FSx FVx
Medic-Alert 100 MAx MHx
Hazard-Alert 150 PAx PHx
Tornado-Alert 150 PAx PHx
Proc-Mon 200 IAx IRx
Procmon-AR 200 IAx IRx
AC-Loss-Mon 301 ATx ARx
Drill-Switch 604 FIx FKx
Drill-Switch AutoResettable 604 FIx FKx