Programming
MS-5UD/MS-10UD Series PN 52626:B 8/01/2008 93
Ademco Contact ID Format - Primary Central Station Phone Number
The information shown in Table 3.3 is automatically programmed for the Primary Central
Station phone number Event Codes when Ademco Contact ID Format is selected. To disable
event reporting, select the desired Event Code to be disabled and press 0 or Clear and then
Enter to disable it. (Enter must be pressed to save the selection. Pressing Escape will not save
the selection).
Table 3.3 Ademco Contact ID Primary # Event Codes
Event Description Event Code Settings
Active
Primary # Zone 1 - 10 Alarm 115
Primary # Zone 1 - 10 Disabled 570
Primary # Drill 604
Primary # AC Fault 301
Primary # Zone 1 - 10 Fault 380
Primary # Zone 1 - 10 Dirty 380
Primary # Earth Fault 310
Primary # Low Battery Fault 302
Primary # No Battery Fault 311
Primary # Telco Primary Line Fault 351
Primary # Telco Secondary Line Fault 352
Primary # NAC #1 Fault 321
Primary # NAC #2 Fault 322
Primary # NAC #3 Fault 326
Primary # NAC #4 Fault 327
Primary # NAC #1 Disable 521
Primary # NAC #2 Disable 522
Primary # NAC #3 Disable 526
Primary # NAC #4 Disable 527
Primary # Charger Fault 300
Primary # Comm Trouble Primary # 354
Primary # Comm Trouble Secondary # 354
Primary # Printer Fault 336
Primary # ANN-Bus Fault 330
Primary # Option Card Fault 333
Primary # CS CALC Fault 304
Future 000
Primary # System Off Normal 308
Primary # System Test Message 602
Primary # System Abnormal Test Message 608
Primary # Upload/Download Request 411
Primary # Upload Successful 416
Primary # Download Successful 412
Primary # Upload/Download Failed 413
Primary # Voice EVAC Fault 330
Primary # Power Supply Sync Fault 300