ACPS-610/E Manual — P/N 53018:A1 07/31/2007 31
Programming the ACPS-610 Configuration and Programming
Figure 3.4 PK-PPS: Label
Label
For greater ease of identification, you may create a label for each power supply. Labels may
have a maximum of 40 characters.
Figure 3.5 PK-PPS: Battery Charger
Battery Charger
Choose the appropriate battery charger current for the systems battery capacity. Refer to
Section 5.2, “Calculating the Battery Requirements”, on page 49 for more information on
determining your system’s battery capacity.
There are three charger current options. Select
2A CHARGE to charge 12 to 55 AH batteries.
Select
5A CHARGE to charge 56 to 200 AH batteries. Select DISABLE CHARGER when the power
supply will not be connected to any batteries or when the batteries will be powered by an
external charger (See page 23).
PK-PPS_Label.jpgBatteryChargerUSa.jpg
NOTE: When the battery charger is disabled, the power output continuous current is 2.5 Amps.