50 ACPS-610/E Manual — P/N 53018:A1 07/31/2007
Power Supply Calculations Calculating the Battery Requirements
5.2.2 Calculating the Battery Size
Use this table to choose the battery size, in amp-hours, needed to support the fire alarm system. The
ACPS-610 can charge batteries from 12 to 200 AH. Select batteries that meet or exceed the Total
Amp-Hours calculated in Table 5.8 and that are within the acceptable battery charger range. Write
the amp-hours requirements on the Protected Premises label.
Battery Size
Voltage
Rating
Number Required
Part Number
*
* Manufactured to our specifications by WUHAN SOTA ENERTECH, INC.
Backbox
†
(Order Part Number)
† Red version available for some models. Check for availability.
12 AH 12 volts two BAT-12120 CAB-PS1, SBB-A4, SBB-B4,
SBB-C4, SBB-D4, BB-25
26 AH 12 volts two BAT-12260 SBB-A4, SBB-B4,
SBB-C4, SBB-D4, BB-25
55 AH 12 volts two for 55 AH
four for 110 AH
BAT-12550 NFS-LBB
BB-100
100 AH 12 volts two for 100 AH
four for 200 AH
BAT-121000 BB-100
BB-200
Table 5.9 Selecting the Battery Size
NOTE: Battery size is limited to 12 AH minimum to 200 AH maximum using the internal
ACPS-610 battery charger.