ACPS-610/E Manual — P/N 53018:A1 07/31/2007 35
Programming the ACPS-610 Configuration and Programming
Figure 3.9 PK-PPS: Trouble Reporting
Trouble Reporting
Select the trouble reporting option. When the power supply is configured for US trouble
reporting options, the panel will report a trouble message at the base address. Choose a US AC
Fail Delay time (
0, 2 HOURS, 8 HOURS, or 16 HOURS) from the drop-down menu. In FlashScan
systems, the panel will display the specific trouble type (AC Fail, Battery Low, Battery High,
Earth Fault, or Charger Failure) at the power supply’s base address. In CLIP systems, the panel
will only display a general trouble at the power supply’s base address.
When the power supply is configured for Canadian trouble reporting, the panel displays a
specific trouble message for at the AC Fail, Battery, Earth Fault, and Charger Fail addresses
(See Table 3.1). If a Canadian code type is selected, trouble reporting will be set automatically
to Canadian.
Figure 3.10 PK-PPS: Summary
Summary
The Summary screen displays all of your previous selections and the resulting SLC address
consumption. Review this summary screen before downloading and ensure that the proper
number of consecutive addresses are reserved. You may use the
BACK button to edit any of
your selections. Click the
FINISH button to save your changes to the database.
PK-PPS_TroubleReport.jpg
PK-PPS_Summarya.jpg