ACPS-610/E Manual — P/N 53018:A1 07/31/2007 47
DC Current Draw Calculations Power Supply Calculations
Table 5.4 DC Current Draw Calculations, Output 4
Table 5.5 Total ACPS-610 DC Current Draw Calculations
OUTPUT 4
CATEGORY
COLUMN A
Standby Current (amps)
COLUMN B
Alarm Current (amps)
Qty X current draw= Total Qty X current draw= Total
Power Supervision Relays
(EOLR-1)
X = A X = A
4-Wire Smoke Detectors X = A X = A
4-Wire Smoke Detectors X = A X = A
Annunciators X = A X = A
Auxiliary Devices X = A X = A
Auxiliary Devices X = A X = A
Auxiliary Devices X = A X = A
Notification Appliances
Not Applicable
X = A
Notification Appliances X = A
Notification Appliances X = A
Sum each column for totals
Output 4
Standby Current
Draw total:
A
Output 4
Alarm Current
Draw total:
A
Column A
Standby Current
(amps)
Column B
Alarm Current
(amps)
ACPS-610 Power Supply 0.09 A 0.09 A
Output 1 (Enter Totals from Table 5.1) AA
Output 2 (Enter Totals from Table 5.2) AA
Output 3 (Enter Totals from Table 5.3) AA
Output 4 (Enter Totals from Table 5.4) AA
Sum each column for totals
Standby
Current Draw
total:
A Alarm
Current
Draw total:
A
Note: STANDBY CURRENT TOTAL cannot exceed 6.0A/10.0A or 1.5 A/2.5 A. for any single output.
A
LARM CURRENT TOTAL cannot exceed 6.0 A or 1.5 A for any single output.