NFS2-3030 Listing Document — P/N LS10006-051NF-E:F2 5/19/2022 13
1.6 ULC Remote Connection Feature
ULC requires that devices such as TM-4 and UDACT/UDACT-2 be disconnected during annual testing to prevent transmission of false alarms.
Disconnecting TM-4 for Annual Testing: Follow standard installation procedures as described in the TM-4 installation documentation. To disable
reporting, slide SW4 Disable All Output switch from “Enable” to “Disable.” Refer to TM-4 documentation for product drawing.
Disconnecting UDACT/UDACT-2 for Annual Testing: Install UDACT/UDACT-2 as the last device on the EIA-485 line, with a listed key switch
such as AKS-1B installed on the EIA-485 line. In this case only, install the ELR between the EIA-485 wires just in advance of the key switch (refer to
Figure 12). The key switch should be installed so that key-removed is the closed position; it should be located inside the same backbox as the UDACT/
UDACT-2, as close to the UDACT/UDACT-2 as possible.
1.7 Devices Requiring External Power Supervision
With LCM-320 revision 2.0 and higher, certain type codes have external power supervision (FlashScan only) built into the software. An external
power-supervision relay is required (see Figure 13) unless one of the following type codes is selected for the device:
NOTE: During testing when the key switch is turned, the panel will report a communication failure for the UDACT or UDACT-2’s address.
Control (Blank) Nonreset Ctl Gen Super
Strobe Release Ckt Alarm Pend Gen Trouble
Horn Rel Ckt ULC Gen Alarm Gen Pend
Trouble Pend
3030-UDACT-switch.cdr
UDACT
CPU
NOTE: This illustration is shown with the UDACT. For UDACT-2
setup information, refer to the UDACT-2 Instruction Manual.
Figure 12 Wiring a Key Switch to Disconnect UDACT During Annual Testing
Device to be
Supervised
Non-resettable 24
VDC Power from
a listed source
+
+
SLC from FACP or
LCM/LEM
FCM-1
N.C. Supervision
Relay Contact
Part of EOLR-1
(Not required for FlashScan type
codes that provide built-in power
supervision.)
Power Supervision Relay (EOLR-1)
(Not required for FlashScan type codes that
provide built-in power supervision.)
3030-external-power-suptpH.wmf
Figure 13 Enabling External Power Supervision Using Relays