EasyManua.ls Logo

Honeywell Notifier NFS2-3030 - Active Event Indications

Honeywell Notifier NFS2-3030
76 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
36 NFS2-3030 Listing Document — P/N LS10006-051NF-E:F2 5/19/2022
Panel Timers Programming
Selecting the Panel Timers option on the first Panel Programming screen will display the following panel timer options:
VERIFY TIME: Press to set the Alarm Verification timer. Type in a value of
0-240 (seconds), which will delay initiating devices set for Alarm Verification
from signaling for the amount of time entered. If a second alarm occurs while
the alarm verification timer is counting, the timer will stop and the alarm will
signal immediately. Default: 30 seconds
MAXIMUM VERIFICATION COUNT: Press and enter a value from 0-20 for a
maximum verification count threshold value that applies to detectors set to par-
ticipate in Alarm Verification. A value of zero produces no verification trouble.
When the counter exceeds the threshold value entered, a trouble is generated to
the panel. Default: 20
AC FAIL DELAY: Press to set the timing for the time delay from AC failure to when the
trouble is reported. Type in a value of 1-12 (hours), or select NONE. A value of NONE will
cause immediate notification. Default: 8
SILENCE INHIBIT: Press to enter a value from 0 (disabled) to 5 minutes. This software
timer disables the signal silence key function for the time entered when a fire alarm occurs. The timer starts at the first alarm only; it does not restart
with each new alarm. Default: 0
AUTO SILENCE: Press to enter a value of OFF (no Auto Silence Timer), or a value of 10, 15, or 20 minutes. This global software timer functions
like pressing the Signal Silence key. For example, if a value of
10 is entered, the control panel will silence all active outputs programmed as silence-
able after ten minutes. When Auto Silence activates, special function zone ZF40 will activate and will remain active until a system reset, alarm
resound, or drill (alarm signal on for Canadian applications) is initiated. Default: OFF
VERIFY=PREALARM: Press to enter YES or NO for displaying Prealarm during alarm verification. Default: NO
MORE: Press to proceed to the second Panel Timers screen.
PAS: Press to toggle between the choices of OFF or ON for PAS (Positive
Alarm Sequence).
PRESIGNAL DELAY: Press to enter a value of 00:00 (OFF) or a value of
1:00 to 3:00 minutes (in the format MM:SS, where MM= minutes, SS=sec-
onds). This feature initially causes alarm signals to sound only in specific areas,
monitored by qualified personnel. This allows delay of the alarm for up to 3
minutes after the start of alarm processing. Default: 3:00
DEFAULT TIMERS: Press to activate default settings for the Panel Timers.
NOTE: AHJ approval is required if this value exceeds 60 seconds. This
value cannot exceed 30 seconds for ULC applications.
NOTES: AC FAIL DELAY settings other than 1-3 hours for off-premises notification require the
approval of the local Authority Having Jurisdiction.
The onboard trouble relay (TB3 on the CPU2-3030(CPU2-3030DC for Canada only) will activate and
TM-4s will report according to this setting.
UDACTs and UDACT-2s are notified immediately of AC failure by the panel, regardless of the
panel’s delay setting. Once the UDACT or UDACT-2 receives notification, it operates according to its
own programmed AC Fail Delay reporting schedule.
The AMPS-24, ACPS-610, and ACPS-2406 power supplies must be set to an AC FAIL DELAY value
of 0 (zero) when used with this panel.
NOTE: The value must be 20 minutes for ULC installations.
Panel Timers Screen (1)
PANEL TIMERS
VERIFY TIME: 30 VERIFY=PREALARM: NO
MAXIMUM VERIFICATION COUNT: 00
AC FAIL DELAY: 2 HOURS MORE
SILENCE INHIBIT:00:00
ACCEPT
AUTO SILENCE: OFF BACK
Example: AC Failure occurs at 1:00 p.m. on a panel
with an AC FAIL DELAY setting of 8 hours. The
UDACT/UDACT-2 is set for notification after 6 hours.
Time Event
1:00 p.m. AC Failure. Panel notifies UDACT/
UDACT-2. Panel and UDACT/UDACT-2
timers begin countdown to report time.
7:00 p.m. UDACT/UDACT-2 reports
9:00 p.m. TM-4 reports, TB3 trouble relay activates
AC Fail Delay Example
Panel Timers Screen (2)
PANEL TIMERS
PAS: OFF
PRESIGNAL DELAY: MM:SS
DEFAULT TIMERS
ACCEPT
BACK
Program Setting for: Default:
Verify Time 30 seconds
Max. Verify 20
AC Fail Delay 8 hours
Silence Inhibit 0 (disabled)
Auto Silence Off
Verify=Prealarm No
PAS OFF
Presignal Delay 3 minutes
Default Settings

Other manuals for Honeywell Notifier NFS2-3030

Related product manuals