70 NFS2-640 Operations P/N 52743:L4 06/10/19
Remote Terminal Access Using the CRT-2 for Read Status
From the Read Status menu, you can select options 1-7.
C.3.3 Read Point
From the Read Status menu, select option 1 - Read Point. The CRT-2 displays the following:
Enter the following:
1. Enter the SLC number “1” or “2”.
2. Enter the first letter of the device, using upper case letters.
Detector = “D”
Module = “M”
Zone = “Z”
Special Function = “F”
Releasing Zone = “R”
•E Zone =E
L Zone = “L”
System Parameter = “S”
3. Enter the address or number of the device.
4. Press “
ENTER”.
Example Read points for detectors 1D001 and 1D002 on SLC 1:
C.3.4 Display Devices in Alarm or Trouble
From the “Read Status” menu, select option 2 - Read Alarms/Troubles. The CRT-2 will display the
alarm and trouble history.
Press <1> <ENTER>
Type (n)D(nnn), (n)M(nnn), Z(nn), F(n),, R(n), Ex, Lx or S(n) then hit Enter
SLC number
Address (01-159)
Number
NOTE: Press F5 to scroll forward through a list of devices. Press F6 to scroll back through a list
of devices.
NORMAL SMOKE(PHOTO) INTENSIVE CARE UNIT NURSE LOUNGE Z050 020%A6 6 CV30 1D001
Press <1> <D> <0> <0> <1> <
ENTER>
NORMAL SMOKE (ION) DETECTOR ADDR 1D002 Z002 000%A6 6 ** 1D002
Press <
NEXT>