NFS2-640 Operations P/N 52743:L4 06/10/19 71
Using the CRT-2 for Read Status Remote Terminal Access
The semicolon, a control character in networking applications, separates the hour and minute of
events displayed from history. If events display as they occur, a colon separates the hour and min-
ute.
C.3.5 Display All Programmed Points
From the “Read Status” menu, select option 3 - All Points. This option lets you view the status of
all addressable detectors, modules, system parameters, and software zones.
C.3.6 Step-through History
From the “Read Status” menu, select option 4 - Step-through History. This option lets you step
through all history events one at a time.
C.3.7 View All History
From the “Read Status” menu, select option 5 - History ALL. The entire history of events will dis-
play on the screen.
C.3.8 Step-through Alarm History
From the “Read Status” menu, select option 6 - Step-through Alarm History. This option lets you
step through the panel’s alarm history one event at a time.
C.3.9 View All Alarm History
From the “Read Status” menu, select option 7 - Alarm History All. The entire history of alarm
events will display on the screen, from most recent to oldest.
Step through the Alarm History buffer one event at a time by pressing the Next F5 or Prior F6 func-
tion keys.
TROUBL SMOKE(PHOTO) DETECTOR ADDR 1D003 INVREP 01;09P 041615 1D003
TROUBL SMOKE (ION) DETECTOR ADDR 1D004 INVREP 01;09P 041615 1D004
TROUBL HEAT(FIXED) DETECTOR ADDR 1D006 INVREP 01;09P 041615 1D006
TROUBL MONITOR MODULE ADDR 1M041 INVREP 01;09P 041615 1M041
TROUBL IN SYSTEM GROUND FAULT 01;09P 041615 Wed
TROUBL IN SYSTEM BATTERY 01;09P 041615 Wed
Press <2> <
ENTER>
Semicolon
NORMAL SMOKE(PHOTO) DETECTOR ADDR 1D002 Z003 000%A8 8 ** 1D002
NORMAL SMOKE (ION) DETECTOR ADDR 1D003 Z002 020%A6 6 ** 1D003
NORMAL HEAT(FIXED) DETECTOR ADDR 1D006 Z001 050% * 1D006
NORMAL SMOKE(LASER) DETECTOR ADDR 1D099 Z004 000%A6 6 *V00 1D099
OFF RELEASE CKT MODULE ADDR 1M001 ZR00 I** 1M001
NORMAL MONITOR MODULE ADDR 1M001 ZR00 I** 1M001
OFF RELAY MODULE ADDR 1M033 Z000 *FW 1M033
OFF SOFTWARE ZONE Zone 01 Z01
************************ EVENT HISTORY START ***********************************
ALARM: MAN_RELEASE MODULE ADDR 1M065 10:21A 041515 1M065
ALARM: MAN_RELEASE MODULE ADDR 1M065 10:19A 041515 1M065
ALARM: MAN_RELEASE MODULE ADDR 1M065 03:20P 041415 1M065
ALARM: SMOKE (ION) DETECTOR ADDR 1D129 03:20P 041415 1M065
Press <6> <
ENTER>