66 NFW-100X Manual — P/N LS10131-001NF-E:C 7/25/2018
Programming Master Programming Level
While viewing one of the Control Type screens, select the type of control module being programmed by pressing the corresponding key-
pad number key. The display will return to the Edit Control Screen #2 and indicate the new type selection.
The following table contains control module type codes and their functions which are displayed in the Control Type screens:
Silenceable
The Silenceable selection allows the programmer to select whether output devices connected to the control
module can be silenced, either by pressing the Alarm Silence key or by enabling Autosilence. Pressing the 3
key while viewing Edit Control Screen #2 will enable the Silenceable feature causing the display to read
Silenceable Yes. Repeated presses of the 3 key will cause the display to toggle between Silenceable Yes and
Silenceable No.
Walktest
The Walktest feature allows one person to test the system devices without the necessity of manually reset-
ting the control panel after each device activation. To enable devices, which are connected to a control mod-
ule, for the Walktest feature, press 1 while viewing the Edit Control Screen #3 until the display reads
Walktest Yes. Each press of the 1 key will cause the display to toggle between Walktest Yes and Walktest No.
Refer to “Walktest” on page 114 for additional information.
Zone Assignment
A maximum of five zones can be programmed to each addressable control module. Pressing 2 while viewing Edit Control Screen #3 dis-
plays the following screen:
Note that Z*** represents the Zone Number(s) corresponding to this device. The factory default for an unprogrammed device is Z000 for
general alarm zone. A flashing cursor will appear on the first 0 to the left. Enter the three digit number corresponding to the zone that is
to be assigned to this device. The cursor moves to the next Z*** designation. Continue entering zone assignments or the remaining zones
can be left blank or programmed as general alarm zones Z000. When all desired changes have been made, press the Enter key to store the
zone assignments. The display will return to the Edit Control Screen #3.
Noun/Adjective
The Noun/Adjective selection allows the programmer to enter specific descriptors about the control module
currently being programmed. Pressing 1 while viewing Edit Control Screen #4 will cause the following
screen to be displayed:
NOTE:
A control relay module set to the Resettable Power type will follow the main circuit board 24 VDC resettable power unless the
control relay module is disabled.
Control Type Special Function
Bell Circuit NAC Type - supervised
Horn Circuit NAC Type - supervised
Sounders NAC Type - supervised
Relay Ignore Open Circuit
Strobe Circuit NAC Type - supervised
Control NAC Type - supervised
Resettable Power
1
1 When using a control relay module to supply resettable power to
conventional 2-wire smoke detectors, the addressable monitor module
must be programmed for Smoke-Conventional operation
Relay Type - Ignore Open Circuit
HVAC Shutdown RLY
2
2 For HVAC SHUTDOWN description, refer to “Control Module
Operation” on page 144.
Relay Type - Ignore Open Circuit
HVAC Shutdown NAC
2
NAC Type - supervised
EDIT CONTROL
1=ENABLED
2=TYPE
3=SILENCEABLE
Edit Control Screen #2
EDIT CONTROL
1=WALKTEST
2=ZONE ASSIGNMENT
000 
Edit Control Screen #3
ZONE ASSIGNMENT
Z000   
Zone Assignment Screen
EDIT CONTROL
1=NOUN/ADJECTIVE
2=DESCRIPTION
Edit Control Screen #4
1=STANDARD ADJECTIVE
2=STANDARD NOUN
3=CUSTOM ADJECTIVE
4=CUSTOM NOUN
Noun/Adjective Screen