EN2R-9031 0402R15-NE 16
SYSTEM OPERATION  S4565C, D, R, T
General
Lock-out reset
The S4565C, D, R, T ignition controls can be reset by either 
depressing the internal/external reset button (suffix C and D) 
or by interrupting the permanent life (suffix R, and T).
If a first reset is not succesful, wait at least 15 seconds before 
attempting another one.
NOTE 5.: When first starting, the ignition control can be in 
the lock-out condition, depress the reset button 
to free the ignition control. After a reset an 
extended waiting time will occur.
NOTE 6.: If during normal use the reset button is pressed, 
the gas valves close and the ignition control 
starts a new sequence after releasing the reset 
button.
NOTE 7.: If permanent alarm output:neon indicator with 
integral resistor >150 kΩ (max 1 mA)
Suffix C and R (see Fig. 9.)
When there is a call for heat the fan starts running through 
the no air position of the air proving switch.
If an external LPG valve is connected, this will be energized.
When sufficient air flow is proven by the air proving switch, a 
self check period (T
c 
) plus a prepurge period (T
p
) elapse 
before the gas valve and built-in ignition or external ignition 
transformer (optional) are switched on.
The ignition spark ignites gas and resulting flame is detected 
by the flame rod.
Internal or external ignition is switched off.
After flame establishment a predetermined, extended ignition 
time can be included.
If flame is not established within the safety time (T
s
), the 
ignition control locks out.
If the flame is lost during normal run, the ignition control 
repeats the start sequence with prepurge.
If no air is proven by the air proving switch within the 
prepurge time (T
p
), the ignition control stays in waiting mode 
with fan running.
Suffix D and T (see  Fig. 10.)
When there is a call for heat the fan starts running through 
the no air position of the air proving switch.
If an external LPG valve is connected, this will be energized.
When sufficient air flow is proven by the air proving switch, a 
a self check period (T
c 
) plus a prepurge period (T
p 
) elapse 
before the pilot gas valve and built-in ignition or external 
ignition transformer (optional) are switched on.
The ignition spark ignites pilot gas and resulting flame is 
detected by the flame rod.
Internal or external ignition is switched off.
After flame establishment a predetermined, extended ignition 
time can be included.
If flame is not established within the safety time (T
s
), the 
ignition control locks-out.
If the flame is lost during normal run, the ignition control 
repeats start sequence at prepurge.
If no air is proven by the air proving switch within the 
prepurge time (T
p
), the ignition control stays in waiting mode 
with fan running.
WARNING
Do not interchange air proving switch wiring in order 
to prevent malfunctioning