EN2R-9031 0402R15-NE 30
SYSTEM OPERATION S4565AD, BD, CD, DD, PD, QD, RD, SD, TD “2000” SERIES
General
The S4565AD, BD, CD, DD, PD, QD, RD, TD ignition controls 
can provide both closed-loop sparking and sparking to 
ground.
The S4565SD ignition circuit and rectifier provides closed-
loop sparking.
Lock-out reset
The ignition control can be reset by either depressing the 
internal/external reset button (suffix AD, BD, CD and DD) or 
by interrupting the permanent life (suffix PD, QD, RD and 
TD).
NOTE 11.: When first starting, the ignition control can be in 
the lock-out condition, depress the reset button 
to free the ignition control. After a reset an 
extended waiting time will occur.
NOTE 12.: If during normal use the reset button is pressed, 
the gas valves close and the ignition control 
starts a new sequence after releasing the reset 
button.
NOTE 13.: If permanent alarm output:neon indicator with 
integral resistor >150 kΩ (max 1 mA).
Do not connect any electrical load to the heat 
demand input, it will influence proper functional-
ity.
Suffix AD and PD (see Fig. 35.)
When there is a call for heat a self check period (T
c
) plus 
waiting period (T
w
) elapse before the built-in igniter and gas 
valve are switched on.
The ignition spark ignites gas and resulting flame is detected 
by the flame rod.
After flame establishment a predetermined, extended ignition 
time can be included.
If flame is not established within the safety time (T
s
), the 
ignition control locks out.
If the flame is lost during normal run, the ignition control 
repeats start sequence.
Suffix BD and QD (see Fig. 36.)
As AD and PD except flame relay contact or opto is activated 
after flame detection.
NOTE 14.: The hour counter is energized when the valve is 
energized. It can be used as an output signal.
Suffix CD and RD (see Fig. 37.)
When there is a call for heat, self check period (T
c
) plus 
waiting period (T
w
) elapse if the air proving switch is in the no 
air position.
After T
c
 + T
w
 the fan starts running.
When sufficient air flow is proven by the air proving switch, 
the built-in igniter and gas valve are switched on.
The ignition spark ignites gas and resulting flame is detected 
by the flame rod.
After flame establishment a predetermined, extended ignition 
time can be included.
If flame is not established within the safety time (T
s
), the 
ignition control locks out.
If the flame is lost during normal run, the ignition control 
repeats start sequence.
If no air is proven by the air proving switch, the ignition control 
stays waiting (optional lock out on no air can be included).
Suffix DD and TD (see Fig. 38.)
As CD and RD except flame relay contact or opto is activated 
after flame detection.
Suffix SD (see  Fig. 30.)
If line voltage is applied between pin 5 (line valves) and pin 9 
(N), the gas valve is switched on.
If the line voltage is applied between pin 4 (line ignition) and 
pin 9 (N) the build in igniter is switched on.
The igniter circuit is fed during the negative half wave of the 
mains.
Pin 8 is present but not intended for use. It is connected with 
a resistor (100 Ω) to pin 5.
Ignition circuit must be on shorter than 10 s in an application 
with single ignition trial.
Gas/air application
For gas/air application without dynamic aircheck, the 
S4565AD, BD, PD or QD can be used. 
In this application the fan is connected between pin 4 and 5 
and will start when a call for heat is present. The waiting 
period now acts as a prepurge time.
When the call for heat disappears or when the ignition control 
goes in lock-out, the fan will be switched off.