SPECIFICATIONS S4565AF, BF, CF, DF, PF, QF, RF, TF
Model
Suffix AF: atmospheric, direct burner ignition
Suffix BF: atmospheric, intermittent pilot burner ignition
including safety timer
Suffix CF: fan assisted, direct burner ignition
Suffix DF: fan assisted, intermittent pilot burner ignition
including safety timer
Suffix PF: as AF except volatile lock-out
Suffix QF: s BF except volatile lock-out
Suffix RF: as CF except volatile lock-out
Suffix TF: as DF except volatile lock-out
Supply voltage
220 ... 240 Vac, 50/60Hz (-15%,+10%)
Power consumption
4 VA
Humidity
90% RH max. at 40°C
Ambient temperature
-15 ... 60°C
Electrical rating (see also note 17.)
Alarm: 220 ... 240 Vac, 50/60Hz, 1 A,
cos ϕ > 0.6 or max 1 mA
Fan: 220 ... 240 Vac, 50/60Hz, 1 A,
cos ϕ > 0.6
LPG outdoor valve: 220 ... 240 Vac, 50/60Hz, 1 A,
cos ϕ > 0.6
Second main valve: 220 ... 240 Vac, 50/60Hz, 1 A,
cos ϕ > 0.6
Electrical connection
High voltage spark: 2.8 x 0.5 mm spade terminal
Optional: 4 mm round terminal
Flame sensing: 4.8 x 0.8 mm spade terminal or 2.8 x
0.5 mm spade terminal for combined
high voltage spark/flame sensing
PCB connectors: Molex 3003 series suitable for
Molex 3001 female cable connector
Housing (degree of protection)
See:
accessories for degree of protection page 7..
replacement parts and accessories page 66..
Timing (depending on O.S. number)
Self check time (T
c
): 1.5 s
Waiting time (T
w
): 0 ... 30 s
Safety time (T
s
): 3.5 ... 55 s
Extended spark ignition time
and stabilisation time: 0 ... T
s
(depending on elaps of safety time)
Flame sensing
Min flame current: 0.9 µA
Response time on: > 0.2 s
Response time off (T
FR
): < 1 s
Ignition
Spark voltage: > 12 kV at 40 pF load
(depending on O.S. number)
Spark energy: 3 ... 15 µAs
Repetition rate: 2.5 ... 60 Hz
(depending on O.S. number)
Max. spark gap: 3.5 mm
Length flame sensing cable
1 m maximum
Length ignition cable
0.5 m max.
Length of wiring for external components
1 m max.