EN2R-9031 0402R15-NE 42
SPECIFICATIONS S4565PV, QV, RV, TV
General
The S4565PV, QV, RV, TV are multitrial volatile ignition
controls in accordance with EN 298. The S4565RV and TV
are fan assisted versions with or without prepurge, (reset by
means of interrupting the permanent live or by a reset
switch). Non volatile lock-out of S4565PV, QV, and S4565RV,
TV without prepurge are obtained if the status output is
used to store the lock-out status in the comfort boiler control
e.g. with the use of EEPROM. (see Fig. 58.)
The alternative S4565RV, TV versions with prepurge option
do not contain an independent manual reset function, (reset
by means of interrupting the heat demand).
Model
Suffix PV: atmospheric, direct burner ignition,
volatile lock-out
Suffix QV: as PV but with status or flame relay output
Suffix RV: fan assisted, direct burner ignition,
volatile lock-out
Suffix TV: as RV but with with status or flame relay output
Supply voltage
230 Vac, 50/60 Hz
Power consumption
4 VA
Humidity
90% RH max. at 40°C
Ambient temperature
-15 ... 60°C
Electrical rating (see also note 19.)
Fan: 230 Vac, 50/60 Hz, max 1 A, max cos ϕ
> 0.6
Flame relay contact: 230 Vac, 50/60 Hz, max 1 A,
cos ϕ > 0.6
Gas valve: 210 Vdc, 50 mA
Reset switch: 15 Vdc, 200 mA, live part!!!!!
Status opto coupler: open collector +5 V, 10 k
logic 1 = 0 V
logic 0 = 5 V
50 Hz = block signal between
0 V and 5 V with about 50% duty cycle.
External igniter
(optional): suitable for AC1A199.01 only, 230 Vrac
6 mA, not accessible (IP 00)
Electrical connection
High voltage spark: 2.8 mm spade terminal
Flame sensing: 4.8 mm spade terminal
PCB connectors: Molex 3003 series suitable for Molex
3001 female cable connector
Gas valve: intended for use onto VK41.. series gas
controls
CAUTION
VK41.. gas control needs to be properly earthed by
means of the external faston connection on the top of
the gas control.
Housing (degree of protection)
See:
accessories for degree of protection page 7..
replacement parts and accessories page 66..
Timing (depending on O.S. number)
Self check time (T
c
): 0 ... 2 s
Waiting time (T
w
): 0 ... 15 s
Prepurge time (T
p
): 0 ... 15 s
Safety time (T
s
): 3 ... 10 s
Number of start trials: 1, optional 2 or 3; 2 or 3 only in
combination with appropriate
waiting or prepurge time
Flame sensing
Min flame current for
phase dependent systems: 0.9 A
Response time on: > 0.2 s
Response time off (T
FR
): < 1 s
Ignition
Spark voltage: > 15 kV at 40 pF load
(depending on O.S. number)
Spark energy: 5 ... 15 µAs
(depending on O.S. number)
Repetition rate: 15 Hz
Maximum spark gap: 3.5 mm
Length flame sensing cable
1 m max.
Length ignition cable
0.5 m max.
Length of wiring for external components
1 m max.
Remark
Optional integrated flame relay available with safe separation
or opto coupler with safe separation according EN 60730.
WARNING
Opto coupler interface needs a debounce
time > 500 ms in order to prevent noise caused by
transients on mains or by status transitions.
Opto coupler status output
After heat demand during waiting time (T
w
) or prepurge
time (T
p
) the status signal must be logic 0.
After the waiting time (T
w
) and without flame the status
signal must be logic 1.
After flame detection the status signal must be 50 Hz.
If after the safety time (T
s
) there is no flame detection, the
ignition control goes to volatile lock-out. The status signal
is logic 0.
If high limit (LM) opens during operation the status signal
becomes logic 0. The ignition control makes a restart but
the status signal stays logic 0 during the safety time (T
s
).
This is the high limit indication status. The ignition control
goes to volatile lock-out. The comfort boiler control has to
store this status in a semi permanent memory in order to
achieve non volatile lock-out. Line voltage interruptions
may not cause data loss.
Table 1. Status output
Normal sequence 0 - 1 - 50 Hz
No flame sequence 0 - 1 - 0
High limit sequence during retrial 0 - 0 - 0