EN2R-9031 0402R15-NE 54
SPECIFICATIONS S4585D
Model
Suffix D: fan assisted, intermittent pilot burner ignition
Supply voltage
220 ... 240 Vac, 50/60 Hz (-15%, +10%)
Power consumption
4 VA
Humidity
90% RH max. at 40°C non condensing
Ambient temperature
0 ... 60°C
Electrical rating
Fan: 220 ... 240 Vac, 50/60 Hz, 1 A,
cos ϕ > 0.6
No flame indicator: 220 ... 240 V, 1 mA max
Electrical connection
High voltage spark/flame
sensing single rod: 2.8 x 0.5 mm spade terminal
PCB connectors: Molex 3003 series suitable for
Molex 3001 female cable
connector
Housing (degree of protection)
See:
accessories for degree of protection page 7..
replacement parts and accessories page 66..
Timing (depending on O.S. number)
Self check time (T
c
): 1.5 s
Safety time (T
s
): infinite
Flame sensing
Min flame current: 1.0 ∝A
Response time on: > 0.2 s
Response time off (T
FR
): < 1.0 s
Phase-Phase mains
trafo input: 220 ... 240 > 0.1 VA
Ignition
Spark voltage: 12 kV at 40 pF load
(depending on O.S. number)
Repetition rate: 1 ... 4 Hz
Max spark gap: 3.5 mm
Length ignition and flame sensing cable
0.5 m max.
Length of wiring for external components
1 m max.
Recommended flame sensor
Q371/Q385 ”2000 series”/Q389/Q395 intermittent ignition
pilot burner
Maximum pilot burner output
250 Watt
No flame indicator
Required impedance: > 100 kΩ
No flame indication time
T
NF